TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
5
Table 1: N2 Bus Objects
Point Name
TEC Point
Type/
Address
N30/NAE
Object
Type
BAS Model
Point Type
Override Range
Room Temp
a
ADI-1
N2 AI
CSAD
32 to 122
°
F (0 to 50
°
C)
Aux Temp / Outdoor Temp
a
ADI-2
N2 AI
CSAD
-40 to 122
°
F (-40 to 50
°
C)
Heating SP
a, g
(Occupied Heating SP)
ADI-3
N2 AO
CSAD
40 to 90
°
F (4.5 to 32
°
C)
Cooling SP
a, g
(Occupied Cooling SP)
ADI-4
N2 AO
CSAD
54 to 100
°
F (12 to 37.5
°
C)
Setback Heating SP
a, g
(Unoccupied Heating SP)
ADI-5
N2 AO
CSAD
40 to 90
°
F (4.5 to 32
°
C)
Setback Cooling SP
a, g
(Unoccupied Cooling SP)
ADI-6
N2 AO
CSAD
54 to 100
°
F (12 to 37.5
°
C)
Minimum Heat SP
ADI-7
N2 AI
CSAD
40
°
F (4.5
°
C)
Maximum Heat SP
a
ADI-8
N2 AO
CSAD
40 to 90
°
F (4.5 to 32
°
C)
Minimum Cool SP
a
ADI-9
N2 AO
CSAD
54 to 100
°
F (12 to 37.5
°
C)
Maximum Cool SP
ADI-10
N2 AI
CSAD
100
°
F (37.5
°
C)
Fan
a
BD-1
N2 BO
CSBD
0 = Auto, 1 = On
Mode
a
BD-2
N2 MSO
d, e
CSMS
0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
Occupancy
a
BD-3
N2 BO
CSBD
0 = Unoccupied, 1 = Occupied
W1 State
BD-4
N2 BI
CSBD
0 = Off, 1 = On
W2 State
BD-5
N2 BI
CSBD
0 = Off, 1 = On
Y1 State
BD-6
N2 BI
CSBD
0 = Off, 1 = On
Y2 State
BD-7
N2 BI
CSBD
0 = Off, 1 = On
G State – Fan
BD-8
N2 BI
CSBD
0 = Off, 1 = On
Temp Units
a, c
(Local Display Only)
BD-9
N2 BO
See
Footnote c.
0 =
°
C, 1 =
°
F
Occupancy Override
BD-10
N2 BI
CSBD
0 = No Override, 1 = Override
DI1
b, f
BI-1
N2 BI
CSBI
0 = Off, 1 = On
Temp Alarm
b
BI-2
N2 BI
CSBI
0 = Normal, 1 = Alarm
DI2
b, f
BI-3
N2 BI
CSBI
0 = Off, 1 = On
Notes:
a.
Commandable.
b.
Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out.
c.
On the Metasys NCM system, map BD9
Temp Units Mode
as a Binary Output (BO) object with Auto Restore and
Local Control set.
d.
The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).
e.
When defining the N2 MSO object, select TEC Mode from the States Text Menu. Type 4 for the TEC2103-2
thermostat
.
f.
The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as
None
through the local interface at the thermostat.
g.
The Heating and Cooling SP cannot be overridden simultaneously (this also applies to the Unocc Heating SP and
Unocc Cooling SP). The overridden setpoint must be released prior to overriding the other setpoint. Additionally, if one
setpoint is overridden, the other setpoint may be automatically adjusted by the TEC2103-2 thermostat to maintain the
minimum deadband between the two setpoints.