background image

 

6

    TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions 

The Controller Point Type is the fixed-point definition inside the controller. The BAS Model Point type is the definition inside 
the model file. Use an NCM CS object to retrieve the data. 

The most recent N2 command received by any of the N2 Bus Objects listed in Table 1 controls the thermostat. 

If an AD object is overridden by the Metasys system, all local changes attempted through the thermostat keypad for that AD 
object are ignored until the override is released. For example, if the Metasys system sends a write command to turn System 
Mode Off, then the occupant selects System Mode On at the TEC keypad, the TEC ends up with the System Mode On; 
however, if the Metasys system sends an override command to turn System Mode Off, then the occupant selects System 
Mode On at the TEC keypad, the TEC keeps the System Mode Off. 

Once an override is released, the AD object may once again be changed through the thermostat keypad, but the thermostat 
does not retain any data entered at the TEC keypad during the override. 

Only one of the setpoints (Heating Setpoint or Cooling Setpoint) can be overridden at a time. 

  The value for Heating SP (ADI-3) and Setback Heating SP (ADI-5) must stay within the limits established in the 

controller by Minimum Heat SP (ADI-7 read-only) and Maximum Heat SP (ADI-8). 

  The value for Cooling SP (ADI-4) and Setback Cooling SP (ADI-6) must stay within the limits established in the 

controller by Minimum Cool SP (ADI-9) and Maximum Cool SP (ADI-10 read-only). 

If a setpoint is overridden, the TEC, if necessary, adjusts the other setpoint to maintain the minimum 2 F° deadband 
between the setpoints. The setpoints can be spread further apart but can never be adjusted closer than 2 F° apart. 

Failure to stay within the limits for a command results in an N2 Negative Acknowledge (NAK) error from the TEC2103-2 
thermostat. 

Overrides take precedence over any local adjustment or command in the TEC2103-2. 

You must not have a Relinquish Default for the setpoints if you want to change them from the thermostat display. 

If there is a Relinquish Default for the setpoints, the Network Automation Engine (NAE) always has an Override for either an 
Adjusted value or the Relinquish Default value. You should use Operator Override and Release Operator Override if you 
want to command the setpoint and release it to local control. 

Once all the NAE commands are released, the Override Status in the Hardware tab should be False. At that time, the user 
should be able to change the setpoint from the local display. 

All overrides are released automatically after 10 minutes of no communications (for example, network cable is removed 
from the TEC causing loss of network communications). 

 

Содержание TEC2103-2

Страница 1: ...thermostat on a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security scr...

Страница 2: ... que dispositif de contrôle de fonctionnement Lorsqu une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l équipement contrôlé ou un autre équipement la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supe...

Страница 3: ... appropriate terminal according to the TEC2103 2 thermostat wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermostat cover to the installed base top side first and install the security screw on the bottom ...

Страница 4: ...or N2 Bus Function Y1 Y2 G RC C RH W1 W2 D1 D2 RS Scom OS N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM Cool 2 Figure 5 TEC2103 2 Thermostat Wiring Schematic Connecting the N2 Bus To connect the N2 Bus 1 Observe the polarity when connecting the N2 Bus wires to the TEC2103 2 thermostat Note An End of Line EOL is not needed on ...

Страница 5: ...BI CSBD 0 Off 1 On G State Fan BD 8 N2 BI CSBD 0 Off 1 On Temp Unitsa c Local Display Only BD 9 N2 BO See Footnote c 0 C 1 F Occupancy Override BD 10 N2 BI CSBD 0 No Override 1 Override DI1b f BI 1 N2 BI CSBI 0 Off 1 On Temp Alarmb BI 2 N2 BI CSBI 0 Normal 1 Alarm DI2b f BI 3 N2 BI CSBI 0 Off 1 On Notes a Commandable b Can be a Change of State COS alarm to the BAS or N2 Dialer Module NDM to initia...

Страница 6: ...stablished in the controller by Minimum Heat SP ADI 7 read only and Maximum Heat SP ADI 8 The value for Cooling SP ADI 4 and Setback Cooling SP ADI 6 must stay within the limits established in the controller by Minimum Cool SP ADI 9 and Maximum Cool SP ADI 10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpo...

Страница 7: ... to manually scroll to the next parameter on the menu When left unattended for 45 seconds the display resumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location...

Страница 8: ...ving the front cover and pressing the configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 2 Installer Configu...

Страница 9: ... Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with the input Service A Service alarm is displayed Filter A Filter alarm is displayed RemOVR Remote Override OVR contact This disables all override menu functions of the thermostat The override function is now cont...

Страница 10: ... for instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection is activated even if the thermostat is set to the Off System Mode If frost protection is active it is displayed as an alarm Frost on with the backlight lit on the Status Display Menu To en...

Страница 11: ...m Heating Stage Cycles per Hour Heat cph section for instructions Setting the Maximum Heating Stage Cycles per Hour Heat cph The heating cycles per hour establishes the maximum number of times the equipment or stages are turned on and off in one hour The selection ranges from three to eight cycles per hour Note A higher number of heating cycles per hour results in more accurate temperature control...

Страница 12: ...ting the N2 Address N2 addr To adjust the N2 address adjustable from 1 to 253 while in the Installer Configuration Menu 1 Answer NO to all prompts until the setting the N2 address prompt appears in the display Press YES to set the address 2 Use the UP DOWN arrow keys to display the desired address Press YES to store the address The display now shows the temporary occupancy time prompt See the Esta...

Страница 13: ...w keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the heating lockout prompt See the Setting the Heating Lockout H lock section for instructions Setting the Heating Lockout H lock This feature disables heating operation based on auxiliary or outdoor air temperature requires temperature sensor to be connected to the Auxiliary Outdoor Air Sensor terminal OS for t...

Страница 14: ...the first prompt 2 Press YES to enable the temporary override The TEC2103 2 thermostat returns to the Status Display Menu When scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu 1 Answer NO to all prompts until the Resume Schedule ...

Страница 15: ...he temporary setpoint for the current mode of operation Note Whether the thermostat is heating or cooling the respective setpoint will be temporarily adjusted Note To toggle between the temporary heating and cooling setpoints press the NO key while changing the temporary setpoints Note If a setpoint is overridden over the N2 network it appears the setpoint value can be changed through the TEC2103 ...

Страница 16: ...upied and unoccupied periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods Smart Fan Mode smart Energizes the fan all the time for occupied periods and only on a call for heating and cooling in unoccupied periods This is the default setting To set the fan mode while in the Main User Menu...

Страница 17: ...pply power to the TEC2103 2 thermostat N2 cable runs are broken Locate and correct the wiring Device type is incorrect TEC2103 2 thermostat address must be VND device type Entire N2 Bus is offline EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Computer PC or 120 VAC source Plug MM CVT101 into PC or plug it into a 120 VAC so...

Страница 18: ...6 x 29 mm Shipping Weight 0 75 lb 0 34 kg UL and cUL Listing File E27734 with CCN s XAPX US UL 873 and XAPX7 Canada CSA C22 2 No 24 FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this eq...

Страница 19: ... GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Contr...

Отзывы: