Enabling Keypad Lockout (Lockout) 

The T600MSP-2 thermostat has three levels of keypad 
lockout. The levels and degree of lockout are shown in 
Table 2. 

To set the keypad lockout level while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the keypad lockout 

setup prompt appears in the display. Press YES to 
enter the keypad lockout menu. 

2.  Use the UP/DOWN arrow keys to locate the 

desired lockout level. Press YES to select the 
level. 

The display now shows the power delay setup prompt. 
See the 

Setting the Power-up Delay (Pwr del)

 section 

for instructions. 

Table 2: Keypad Lockout Levels 

 

Level 0 

Level 1 

Level 2 

Resume to 
Scheduling 

Yes access 

Yes access 

No access 

Temperature 
Setpoints 

Yes access 

No access 

No access 

System Mode 
Setting 

Yes access 

Yes access 

No access 

Fan Mode 
Setting 

Yes access 

Yes access 

No access 

Schedules 
Setting 

Yes access 

No access 

No access 

Clock Setting 

Yes access 

Yes access 

Yes 
access 

Schedule 
Hold 

Yes access 

Yes access 

No access 

 

Setting the Power-up Delay (Pwr del) 

On initial power-up of the T600MSP-2 thermostat (or 
each time power is removed and reapplied), there is a 
delay before any operation is authorized (fan, cooling, 
and heating). The delay time is adjustable between 10 
and 120 seconds. This parameter also can be used to 
sequence the start-up of multiple units in one location. 

Note: 

When adjusting the time with the UP/DOWN 

arrow keys, holding the keys down changes the time 
by 10-second intervals. 

To set the delay time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the power delay 

setup prompt appears in the display. Press YES to 
enter the power delay setup menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

power-up delay setting. Press YES to store the 
setting. 

The display now shows the frost protection setup 
prompt. See the 

Enabling Frost Protection (Frost pr)

 

section for setup instructions. 

Enabling Frost Protection (Frost pr) 

Frost protection establishes a minimum heating 
setpoint of 42

°

F (5.5

°

C) to prevent freezing in the zone 

controlled by the thermostat. If enabled, frost 
protection is activated even if the thermostat is set to 
the Off System Mode. If frost protection is active, it 
displays as an alarm (

Frost on

 with the backlight lit) 

on the Status Display Menu. 

To enable frost protection while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the frost protection 

setup prompt appears in the display. Press YES to 
enter the frost protection menu. 

2.  Use the UP/DOWN arrow keys to select 

off

 or 

on

Press YES to store the selection. 

The display now shows the maximum heating setpoint 
prompt. See the 

Setting the Maximum Heating 

Setpoint (Heat max)

 section for instructions. 

Setting the Maximum Heating Setpoint (Heat max) 

The maximum heating setpoint establishes the 
maximum temperature in the heating setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 40 to 90

°

F (4.5 to 32

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the maximum heating setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the maximum 

heating setpoint prompt appears in the display. 
Press YES to enter the maximum heating setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum heating setpoint temperature. Press 
YES to store the value. 

The display now shows the minimum cooling setpoint 
prompt. See the 

Setting the Minimum Cooling Setpoint 

(Cool min)

 section for instructions. 

Setting the Minimum Cooling Setpoint (Cool min) 

The minimum cooling setpoint establishes the 
minimum temperature in the cooling setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 54 to 100

°

(12 to 37.5

°

C). 

T600MSP-2 Programmable Thermostat Installation Instructions    

7

 

Содержание T600MSP-2

Страница 1: ...t cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tab to the right Figure 2 Open the thermostat s PCB to the left 3 Pull out approximately 6 in 152 mm of wires...

Страница 2: ...s and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wi...

Страница 3: ...the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second s...

Страница 4: ...and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Fig...

Страница 5: ...ver and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Inputs DI1 and D...

Страница 6: ...hen the message displays the backlight momentarily lights up TOccTime set Y N Each digital input can be programmed in one of five conditions None No function is associated with the input Service A Ser...

Страница 7: ...e the Enabling Frost Protection Frost pr section for setup instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in...

Страница 8: ...rature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to all...

Страница 9: ...emporary setpoint is entered The range is adjustable from 0 to 12 hours To change the temporary occupancy time while in the Installer Configuration Menu 1 Answer NO to all prompts until the temporary...

Страница 10: ...lue The display now shows the cooling lockout prompt See the Setting the Cooling Lockout C lock section for instructions Setting the Cooling Lockout C lock This feature disables cooling operation base...

Страница 11: ...o the beginning of the menu digital input configuration Operation Programming Operating the T600MSP 2 Once the T600MSP 2 thermostat is configured through the Installer Configuration Menu the thermosta...

Страница 12: ...does not appear Answering YES to this prompt enables the T600MSP 2 thermostat to resume the regular scheduled program and setpoints Schedule set Y N To resume the schedule while in the Main User Menu...

Страница 13: ...setpoints remain in effect for the duration set in the Temporary Occupancy Time parameter TOccTime or until manually released To release the temporary setpoint sooner while in the main User Menu 1 An...

Страница 14: ...ys changes the time in 1 minute increments Holding the keys down changes the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Follow the steps in...

Страница 15: ...e scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermosta...

Страница 16: ...press YES to store the time 4 Press YES to enter the day set menu or NO to enter the clock format menu 5 Use the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to st...

Страница 17: ...al Accessories Includes Mounting Hardware 2 Use the UP DOWN arrow keys to locate the desired permanent hold type or resume schedule Press YES to enter the choice Item Product Code Number Remote Indoor...

Страница 18: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protecti...

Отзывы: