background image

 

Enable/Disable Second Heating Stage (H Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second heating 
stage is not needed. 

To disable or enable the second heating stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting heating 

stages prompt appears in the display. Press YES 
to enter the setting heating stages menu. 

2.  Using the UP/DOWN arrow keys; select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the cooling stage setting 
prompt. See the 

Enable/Disable Second Cooling 

Stage (C Stage)

 section for instructions. 

Enable/Disable Second Cooling Stage (C Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second cooling 
stage is not needed. 

To disable or enable the second cooling stage while in 
the Installer Configuration Menu: 

1. 

Answer NO to all prompts until the setting cooling 
stages prompt appears in the display. Press YES 
to enter the setting cooling stages menu. 

2. 

Using the UP/DOWN arrow keys; select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the heating lockout prompt. 
See the 

Setting the Heating Lockout (H lock) 

section 

for instructions. 

Setting the Heating Lockout (H lock) 

This feature disables heating operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is above 
the heating lockout temperature, heating operation is 
disabled. 

The heating lockout temperature parameter is 
adjustable from -15 to 120

°

F (-26 to 49

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature heating lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating lockout 

prompt appears in the display. Press YES to enter 
the heating lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the cooling lockout prompt. 
See the 

Setting the Cooling Lockout (C lock)

 section 

for instructions. 

Setting the Cooling Lockout (C lock) 

This feature disables cooling operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is below 
the cooling lockout temperature, cooling operation is 
disabled. 

The cooling lockout temperature parameter is 
adjustable from -40 to 95

°

F (-40 to 35

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature cooling lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling lockout 

prompt appears in the display. Press YES to enter 
the cooling lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the number of events prompt. 
See the 

Selecting the

 

Number of Events (2/4event) 

section for instructions. 

Selecting the Number of Events (2/4event) 

This feature sets the number of events per 24-hour 
period that can be programmed into the daily 
schedule. 

Two events selects one occupied and one unoccupied 
period per 24 hours and four events selects two 
occupied and two unoccupied periods per 24 hours. 

To change the number of events in a 24-hour period 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the number of 

events prompt appears in the display. Press YES 
to enter the number of events menu. 

2.  Use the UP/DOWN arrow keys to select 2 or 4 

events. Press YES to store the value. 

The display now shows the auxiliary contact 
configuration prompt. See the 

Configuring the Auxiliary 

Contact (Aux cont)

 section for instructions. 

Configuring the Auxiliary Contact (Aux cont) 

The auxiliary contact is an output that can be used to 
energize peripheral devices (for example, lighting 
equipment, exhaust fans, and economizers). The 
contact can be configured as normally open or 
normally closed and toggles with the internal 
occupied/unoccupied schedule (or the remote NSB 
contact on one of the digital inputs, if used). 

10    

T600MSP-2 Programmable Thermostat Installation Instructions 

Содержание T600MSP-2

Страница 1: ...t cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tab to the right Figure 2 Open the thermostat s PCB to the left 3 Pull out approximately 6 in 152 mm of wires...

Страница 2: ...s and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wi...

Страница 3: ...the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second s...

Страница 4: ...and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Fig...

Страница 5: ...ver and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Inputs DI1 and D...

Страница 6: ...hen the message displays the backlight momentarily lights up TOccTime set Y N Each digital input can be programmed in one of five conditions None No function is associated with the input Service A Ser...

Страница 7: ...e the Enabling Frost Protection Frost pr section for setup instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in...

Страница 8: ...rature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to all...

Страница 9: ...emporary setpoint is entered The range is adjustable from 0 to 12 hours To change the temporary occupancy time while in the Installer Configuration Menu 1 Answer NO to all prompts until the temporary...

Страница 10: ...lue The display now shows the cooling lockout prompt See the Setting the Cooling Lockout C lock section for instructions Setting the Cooling Lockout C lock This feature disables cooling operation base...

Страница 11: ...o the beginning of the menu digital input configuration Operation Programming Operating the T600MSP 2 Once the T600MSP 2 thermostat is configured through the Installer Configuration Menu the thermosta...

Страница 12: ...does not appear Answering YES to this prompt enables the T600MSP 2 thermostat to resume the regular scheduled program and setpoints Schedule set Y N To resume the schedule while in the Main User Menu...

Страница 13: ...setpoints remain in effect for the duration set in the Temporary Occupancy Time parameter TOccTime or until manually released To release the temporary setpoint sooner while in the main User Menu 1 An...

Страница 14: ...ys changes the time in 1 minute increments Holding the keys down changes the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Follow the steps in...

Страница 15: ...e scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermosta...

Страница 16: ...press YES to store the time 4 Press YES to enter the day set menu or NO to enter the clock format menu 5 Use the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to st...

Страница 17: ...al Accessories Includes Mounting Hardware 2 Use the UP DOWN arrow keys to locate the desired permanent hold type or resume schedule Press YES to enter the choice Item Product Code Number Remote Indoor...

Страница 18: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protecti...

Отзывы: