The 

Status Display Menu

 is displayed during normal 

thermostat operation. The menu continually scrolls 
through the following parameters: 

• 

Room Temperature 

• 

Day and Time 

• 

System Mode 

• 

Schedule Status (Occupied/Unoccupied) 

• 

Outdoor Temperature (providing sensor is 
connected and functional) 

• 

Applicable Alarms (the backlight lights up as an 
alarm condition is displayed) 

To temporarily stop the scrolling, press the 
YES/SCROLL key. 

The 

Main User Menu

 is used to access and change 

the thermostat’s basic operating parameters. Access 
the menu by pressing the MENU key during normal 
thermostat operation. 

The 

Installer Configuration Menu

 is used to set up 

the thermostat for application specific operation. 
Access the menu by removing the front cover and 
pressing the configuration key, labeled CONFIG 
(Figure 7). 

Configuring the T600MSP-2 Thermostat 

The T600MSP-2 thermostat ships from the factory with 
default settings for all configurable parameters. The 
default settings are shown in Table 1. To reconfigure 
the parameters, follow the steps in this section for the 
corresponding parameters. To set up the parameters, 
access the Installer Configuration Menu. Access the 
Installer Configuration Menu by removing the front 
cover and pressing the configuration key (Figure 7). 

Exit the Installer Configuration Menu any time by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it, press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

Table 1: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See the 

Enabling Keypad Lockout 

(Lockout) 

section. 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See the 

Setting the Power-up Delay 

(Pwr del) 

section. 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See the 

Enabling Frost Protection 

(Frost pr) 

section. 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See the 

Setting the Maximum Heating 

Setpoint (Heat max) 

section. 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See the 

Setting the Minimum Cooling 

Setpoint (Cool min) 

section. 

 

Sets the Anti-Short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See the 

Setting the Anti-Short Cycle 

Timer (Anticycle) 

section. 

 

Sets the Maximum Heating Cycles per 
Hour 
Default: Four 

(4.0) 

See 

Setting the Maximum Heating 

Cycles per Hour (Heat cph) 

section. 

 

Sets the Maximum Cooling Cycles per 
Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Cooling 

Cycles per Hour (Cool cph) 

section. 

 

Sets the Minimum Heating/Cooling 
Deadband 
Default: 

2.0

°

F (1.1

°

C) 

See the 

Setting the Heating/Cooling 

Deadband (Deadband) 

section. 

 

Determines how the Fan Activates in 
Response to a call for Heat 
Default: Thermostat Controls Fan 

(On)

See the 

Setting the Fan Control 

(Fan cont) 

section. 

Continued on the next page . . .  

DI2
set? Y/N 

Lockout
set? Y/N 

Pwr del
set? Y/N 

Frost pr
set? Y/N 

Heat max
set? Y/N 

Cool min
set? Y/N 

Anticycl
set? Y/N 

Heat cph
set? Y/N 

Cool cph
set? Y/N 

Deadband
set? Y/N 

RoomTemp 
75.0 

°

F

 

Fan cont
set? Y/N 

DI1 
set? Y/N

 

T600MSP-2 Programmable Thermostat Installation Instructions    

5

 

Содержание T600MSP-2

Страница 1: ...t cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tab to the right Figure 2 Open the thermostat s PCB to the left 3 Pull out approximately 6 in 152 mm of wires...

Страница 2: ...s and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wi...

Страница 3: ...the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second s...

Страница 4: ...and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Fig...

Страница 5: ...ver and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Inputs DI1 and D...

Страница 6: ...hen the message displays the backlight momentarily lights up TOccTime set Y N Each digital input can be programmed in one of five conditions None No function is associated with the input Service A Ser...

Страница 7: ...e the Enabling Frost Protection Frost pr section for setup instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in...

Страница 8: ...rature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to all...

Страница 9: ...emporary setpoint is entered The range is adjustable from 0 to 12 hours To change the temporary occupancy time while in the Installer Configuration Menu 1 Answer NO to all prompts until the temporary...

Страница 10: ...lue The display now shows the cooling lockout prompt See the Setting the Cooling Lockout C lock section for instructions Setting the Cooling Lockout C lock This feature disables cooling operation base...

Страница 11: ...o the beginning of the menu digital input configuration Operation Programming Operating the T600MSP 2 Once the T600MSP 2 thermostat is configured through the Installer Configuration Menu the thermosta...

Страница 12: ...does not appear Answering YES to this prompt enables the T600MSP 2 thermostat to resume the regular scheduled program and setpoints Schedule set Y N To resume the schedule while in the Main User Menu...

Страница 13: ...setpoints remain in effect for the duration set in the Temporary Occupancy Time parameter TOccTime or until manually released To release the temporary setpoint sooner while in the main User Menu 1 An...

Страница 14: ...ys changes the time in 1 minute increments Holding the keys down changes the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Follow the steps in...

Страница 15: ...e scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermosta...

Страница 16: ...press YES to store the time 4 Press YES to enter the day set menu or NO to enter the clock format menu 5 Use the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to st...

Страница 17: ...al Accessories Includes Mounting Hardware 2 Use the UP DOWN arrow keys to locate the desired permanent hold type or resume schedule Press YES to enter the choice Item Product Code Number Remote Indoor...

Страница 18: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protecti...

Отзывы: