SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
7
MENU ITEM
DEFINITION
DUCT STATIC PRES CURRENT 2
This is the actual duct static pressure sensed by static pressure transducer 2
when the Unit Controller is programmed for two duct static inputs.
DUCT STATIC PRESS AVERAGE
This parameter displays the average duct static pressure input when the Unit
Controller is programmed for two duct static inputs.
DUCT STATIC PRESS HIGHEST
This parameter displays the higher of the two duct static pressure inputs when
the Unit Controller is programmed for two duct static inputs.
DUCT STATIC PRESS LOWEST
This parameter displays the lower of the two duct static pressure inputs when
the Unit Controller is programmed for two duct static inputs.
DUCT STATIC PRESSURE ACTIVE SP
This is the current derived Duct Static Setpoint that the Primary Unit Controller
is trying to maintain.
DUCT STATIC PRESSURE CURRENT
This is a derived value and is the actual duct static pressure value.
DUCT STATIC PRES RESET BAS
This value is found under the Service key and identifies the duct static reset
signal being communicated from a front end BAS control.
DUCT STATIC RESET - HIGH SETP
This parameter is programmed through the Setpoints key. This is the maximum
Duct Static Control point.
DUCT STATIC RESET-LOW SETP
This parameter is programmed through the Setpoints key. This is the minimum
Duct Static Control point.
ECONO CONTROL OUTPUT
This is a derived value and is the analog output from the Unit Controller to the
Economizer Damper Actuator.
ECONO INSTALLED
This parameter is programmed through the OPTIONS key and tells the Primary
Unit Controller what type of economizer is installed, None, Dry Bulb, Single
Enthalpy, Dual Enthalpy, Waterside.
ECONO METHOD ACTIVE
This is a derived value an indicates which of the available economizer methods
the Primary Unit Controller is using.
ECONO METHOD TO USE
This parameter is programmed through the PROGRAM key and tells the Prima-
ry Unit Controller which of the available economizer options to use. The choices
are Dry Bulb, Single Enthalpy, Dual Enthalpy, Best Available, Waterside.
ECONO SYS STATUS
This is the active status of the economizer system, display shows Normal-
Active, Normal-Inactive, Safety Trip, Safety Fault, Safety lockout, User Disabled;
or None.
ECONOMIZER SYSTEM
This parameter is programmed through the PROGRAM key and is used to turn
the economizer option on or off. The options are User Enable or User Disable.
ECONOMIZER VALVE
This is a derived value and is the analog output from the Unit Controller to the
waterside economizer valve.
ELEC HEAT CAPACITY
This parameter is programmed through the Options key. This parameter is used
to identify the electric heat capacity installed in the unit. The options are 11 KW,
17 KW, 34 KW, 68 KW.
ENTERING WATER - ACTIVE SP
This is a derived value and is the Mixed Air Temp minus the Water Econo Delta.
When the entering water temperature is less than this value the unit uses water-
side economizer.
EVAP LEAVING AIR TEMP HIGH
This parameter is programmed through the Setpoints key. This becomes the
Active Supply Air Temperature Setpoint for a FlexSys unit when it is in the Oc-
cupied Cooling With Bypass mode.
EVAP LEAVING AIR TEMP LOW
This parameter is programmed through the Setpoints key. This becomes the
Active Supply Air Temperature Setpoint for a FlexSys unit when it is in the Under
Floor Temperature Over Ride mode.
EVENT MESSAGE
This parameter identifies the most important current active fault or warning.
FACTORY RUN TEST
This feature is initiated through the Service key and is used to verify the opera-
tion of the unit by exercising all the binary and analog outputs.