![Johnson Controls LSWU025 Скачать руководство пользователя страница 164](http://html.mh-extra.com/html/johnson-controls/lswu025/lswu025_manual_2023363164.webp)
JOHNSON CONTROLS
164
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
DISPLAY TEXT
TYPE
ID
VALUE RANGE
LOCATION
DESCRIPTION
Connexsys
Error Reason
and Valve
Derived
Not for Field Use
Firmware CRC
Derived
0 to 99999
Always
This is the Size of the Code in the
Software and is not for Field Use
Real Time
Control - Lost
and Peak
Derived
The Lost and Peak Time Used by the
Control. This is not for Field Use
Real Time
Control - Peak
5 Sec and
Average
Derived
The Average And Peak Over The
Last 5 Seconds Time Used By The
Control. This is not for Field Use
Real Time
Problem
Derived
Not for Field Use
Real Time
Problem
Number
Derived
Not for Field Use
Real Time
Problem
String
Derived
Not for Field Use
Real Time UI -
Lost and Peak
Derived
The Lost and Peak Time Used by the
User Interface. This is not for Field
Use
Real Time UI
- Peak 5 Sec
and Average
Derived
The Average And Peak Over the Last
5 Seconds Time Used by the User
Interface. This is not for Field Use
Duct High
Static Safety
Digital
Input
J13-8
On / Off
I/O Board
Digital Input from the Duct High Static
Switch
Filter Status
Digital
Input
J13-4
Okay / Change
I/O Board
Digital Input from the Dirty Filter Pres-
sure Switch
Hw/Steam
Frz Stat
Digital
Input
J13-6
Okay / Faulted
I/O Board
Digital Input from the Hot Water
Freezestat
Local Stop
Digital
Input
Tb01-3
Run / Stop
I/O Board
Digital Input that Turns the Unit On
And Off
Alarm
Digital
Output
Tb1-7, 8
Okay / Faulted
I/O Board
Digital Output that is Generated when
there is an Alarm
Occupancy
State
Digital
Input
Tb01-4
Occupied /
Unoccupied
I/O Board
Hardwired Digital Input to Put the Unit
Into the Occupied Mode
Safety Input
Chain A
Digital
Input
J21-2
Okay / Faulted
I/O Board
Digital Input from the Compressor
System A Safety Circuit
Safety Input
Chain B
Digital
Input
J21-5
Okay / Faulted
I/O Board
Digital Input from the Compressor
System B Safety Circuit
Safety Input
Chain C
Digital
Input
J22-2
Okay / Faulted
I/O Board
Digital Input from the Compressor
System C Safety Circuit
Safety Inputs
Chain D
Digital
Input
J22-5
Okay / Faulted
I/O Board
Digital Input from the Compressor
System D Safety Circuit
Safety Inputs
Chain E
Digital
Input
J23-2
Okay / Faulted
I/O Board
Digital Input from the Compressor
System E Safety Circuit
Safety Inputs
Chain F
Digital
Input
J23-5
Okay / Faulted
I/O Board
Digital Input from the Compressor
System F Safety Circuit
TABLE 40 -