SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
7
TABLE 43 -
DEFINITIONS
MENU ITEM
DEFINITION
1ST STAGE COOLING SETPOINT
This parameter is programmed through the Setpoints key. This value is used in
a Constant Volume unit as the Active SAT Setpoint for 1st Stage cooling opera-
tion.
1ST STAGE HEATING SETPOINT
This parameter is programmed through the Setpoints key. This value is used in
a Constant Volume unit as the Active SAT Setpoint for 1st Stage heating opera-
tion.
2ND STAGE COOLING SETPOINT
This parameter is programmed through the Setpoints key. This value is used in
a Constant Volume unit as the Active SAT Setpoint for 2nd Stage cooling opera-
tion.
2ND STAGE HEATING SETPOINT
This parameter is programmed through the Setpoints key. This value is used in a
Constant Volume unit as the Active SAT Setpoint for 2nd Stage heating operation.
ACSD
Anti-Short Cycle (time) Delay is an equipment delay built into the unit operat-
ing software. Time delays are used and not limited to compressor operation (for
example, a compressor has a set amount of time to pass before it can operate
again after being turned off). Time delays are used to protect the compressor
and other operating equipment using them.
ACTIVE SLAB CONTROL
This parameter is programmed through the PROGRAM key. This function allows
heat to be turned on during the transition from Unoccupied to Occupied mode
or Occupied to Unoccupied mode if the under floor conditions of a
FlexSys
system are right for the growth of mold and mildew. The choices are Enabled or
Disabled.
ADAPT MORN WARM UP
This parameter is programmed through the PROGRAM key. Adaptive Morning
Warm Up uses the past three days of warm up times and temperatures to calcu-
late the start time for the current day. This parameter allows the user to enable
or disable this feature.
AIR FLOW
This is a calculated amount of Cubic Feet of Air (CFM) leaving the blower
measured through the Piezometer mounted in the unit. The correct altitude and
K-factory is programmed in the unit to read the correct CFM.
ALARM
This is a binary output that could be used to signal that the Unit Controller was
identified an alarm condition.
AVG PRESS DISCHARGE A
Compressor a has a 15 second load, unload duty cycle. This is the average
discharge pressure over that 15 second period.
AVG PRESS SUCTION A
Compressor a has a 15 second load, unload duty cycle. This is the average suc-
tion pressure over that 15 second period
BYPASS DAMPER POSITION
This is a derived value and is the actual position of the bypass damper, by per-
cent open, in a FlexSys unit.
BYPASS VALVE POSITION
This is the analog output from the Unit Controller to the condenser water bypass
valve.
CLOCK SCHEDULE
This parameter is programmed through the PROGRAM key. This function is
used to turn on the internal clock schedule. The choices are Enabled or Dis-
abled.
COMFORT VENTILATION
This parameter is programmed through the PROGRAM key. This function is only
used on a Constant Volume unit. The Primary Unit Controller monitors the return
air temperature and energizes stages of cooling or heating prior to a demand from
the space. This function is only active when the unit is in the Occupied mode.
COMP STAGING SEQ
This parameter is programmed through the OPTIONS key. This parameter iden-
tifies the type of compressor staging the Unit Controller is to use. The choices
are Simple or Mixed.
SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS