SECTION 5 – SEQUENCE OF OPERATION
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
5
The Unit Controller varies the 0–10 Volt analog output
to the VFD to maintain the “DUCT STATIC PRESS
ACTIVE SP.”
If “DUCT PRESS SENSOR 2” is set to DISABLED,
the Unit Controller uses the analog input identified as
“DUCT STATIC PRESS – CURRENT 1” found at con-
nector J10 – terminal 2 as the active duct static input.
Secondary Duct Pressure Transducer Installed
The Unit Controller can be set up to use a second Duct
Pressure Transducer if the building's system requires it
due to layout and use of duct work. The duct static in-
put depends on the setting of “DUCT PRESS SENSOR
2” (OPTIONS key, SUPPLY SYSTEM subsection) set
to ENABLED.
The “DUCT STATIC HIGH SETP” can never be
greater than the programmed “DUCT PRESS TRANS-
DUCER SPAN” (0.25 "
W.C., 1.25 "W.C., 2.50 "W.C.,
or 5.00 "W.C.
). In this case, both duct transducers have
to be identical for voltages and operating ranges.
If “DUCT PRESS SENSOR 2” is set to DISABLED,
the Unit Controller uses the analog input identified as
“DUCT STATIC PRESS – CURRENT 1” found at con-
nector J10 – terminal 2 as the active duct static input.
If “DUCT PRESS SENSOR 2” is set to ENABLED
and “DUCT PRESS CNTRL” is set to “HIGHEST,”
the Unit Controller uses the higher of analog inputs
identified as “DUCT STATIC PRESS – CURRENT
1” found at connector J10 – terminal 2 and “DUCT
STATIC PRESS – CURRENT 2” found at connector
J10 – terminal 5 as the active duct static input.
If “DUCT PRESS SENSOR 2” is set to ENABLED
and “DUCT PRESS CNTRL” is set to “LOWEST,” the
Unit Controller uses the lower of analog inputs identi-
fied as “DUCT STATIC PRESS – CURRENT 1” and
“DUCT STATIC PRESS – CURRENT 2” as the active
duct static input.
If “DUCT PRESS SENSOR 2” is set to ENABLED
and “DUCT PRESS CNTRL” is set to “AVERAGE,”
the Unit Controller uses the average of analog inputs
identified as “DUCT STATIC PRESS – CURRENT
1”and “DUCT STATIC PRESS – CURRENT 2” as the
active duct static input.
The “DUCT STATIC PRESS ACTIVE SP” can be
varied through the communicated input, DSP_RST_
BAS, AV05. If DSP_RST_BAS is set to 0%, “DUCT
STATIC PRESS ACTIVE SP” is the “DUCT STATIC
RESET HIGH SETP.” If the DSP_RST_BAS is set
to 100%, the “DUCT STATIC PRESS ACTIVE SP”
is the “DUCT STATIC RESET LOW SETP.” When
DSP_RST_BAS is between 0% and 100%, the “DUCT
STATIC PRESS ACTIVE SP” is linearly interpolated
between “DUCT STATIC RESET HIGH SETP” and
the “DUCT STATIC RESET LOW SETP.”
The Unit Controller varies the 0–10 Volt analog output
to the VFD to maintain the “DUCT STATIC PRESS
ACTIVE SP.”
Supply Fan VFD Frequency
The User Interface shows the approximate frequency
of the supply fan VFD under the SUPPLY SYSTEMS
key.
When the Supply Fan binary output is OFF, the SUP-
PLY FAN VFD FREQUENCY shows as 0HZ.
When the Supply Fan binary output is ON, the SUP-
PLY FAN VFD FREQUENCY follows.
60.0 HZ
0 VDC
10 VDC
SUPPLY FAN VFD
FREQUENCY
SUPPLY FAN VFD SPEED
ANALOG OUTPUT
20.0 HZ
FIGURE 64 -
SUPPLY FAN VFD FREQUENCY
LD13299
For example, when the analog output to the Supply
Fan VFD is 0VDC, SUPPLY FAN VFD FREQUEN-
CY shows as 20HZ. When the analog output is 5VDC,
SUPPLY FAN VFD FREQUENCY shows as 40HZ.
When the analog output is 10VDC, SUPPLY FAN
VFD FREQUENCY shows as 60HZ.
High Duct Static Switch Option
The unit can be supplied with a high duct static switch
option. The factory installed switch monitors the dif-
ferential pressure across the supply fan. The high duct
static switch is field adjustable 0.08–4.0 "W.C. The in-
put to the Unit Controller is located at connector J13
– terminal 8.
The following parameter must be programmed through
the User Interface: