![Johnson Controls LSWU025 Скачать руководство пользователя страница 148](http://html.mh-extra.com/html/johnson-controls/lswu025/lswu025_manual_2023363148.webp)
JOHNSON CONTROLS
148
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
TABLE 30 -
COMPRESSOR SYSTEMS (A-F)
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SHOW WHEN
UNIT TYPE IS
Comp Sys* Status
Normal - on / Normal - off / Safety trip / Safety
fault / Safety lockout / user disabled
Derived
Always
Compressor A Load*
0%, 33%, 67%, 100%
Derived
Comp A Only
Comp System* State
1
Stop / Run / Lockout / Auto Reset
Derived
Always
Safety Input Chain*
Okay - faulted
Derived
Always
Avg Pressure
Discharge A
0 to 650 PSIG
Derived
Comp A Only
Suction A
0 to 400 PSIG
Derived
Comp A Only
Pressure
Discharge *
0 to 650 PSIG
Look Up Table
Always
Suction *
0 to 400
Look Up Table
Always
Current Run Time
HH:MM:SS
Derived
Always
Ready To Run
Yes / no
Derived
Always
Ready To Stop
Yes / no
Derived
Always
NOTE:
* May be A-F.