JOHNSON CONTROLS
178
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
RAT_HEAT_
SP
RAT Heating Setp
R/W
AV15
1040
On a VAV or FlexSys Unit this is the Return Air
Temperature Setpoint Used to Determine when
the Unit Should Switch to the Heating Mode (F)
RAT_COOL_
SP
RAT Cooling Setp
R/W
AV23
1048
On a VAV or FlexSys Unit this Value is Used
to Determine when the Unit Should Switch to
the Cooling Mode (F)
RAT_HIGH_
SAT
RAT for High SAT
R/W
AV24
1049
The Return Temperature the Control Uses
when Using Return Air SAT Reset to Switch
to the SAT High Limit Setpoint (F)
RAT_LOW_
SAT
RAT for Low SAT
R/W
AV25
1050
The Return Temperature the Control Uses
when Using Return Air Sat Reset to Switch to
the SAT Low Limit Setpoint (F)
RDY_RUN_
C1A
Ready to Run Comp A
R
BI40
1321
Identifies if Compressor A is Ready to Run if
the Compressor is Off (Yes / No)
RDY_RUN_
C2B
Ready to Run Comp D
R
BI43
1324
Identifies if Compressor D is Ready to Run if
the Compressor is Off (Yes / No)
RDY_RUN_
C3A
Ready to Run Comp E
R
BI44
1325
Identifies if Compressor E is Ready to Run if
the Compressor is Off (Yes / No)
RDY_RUN_
C3B
Ready to Run Comp F
R
BI45
1326
Identifies if Compressor F is Ready to Run if
the Compressor is Off (Yes / No)
RDY_STOP_
C1A
Ready to Stop Comp A
R
BI46
1327
Identifies if Compressor A is Ready to Stop if
the Compressor is Running (Yes / No)
RDY_STOP_
C1B
Ready to Stop Comp B
R
BI47
1328
Identifies if Compressor B is Ready to Stop if
the Compressor is Running (Yes / No)
RDY_STOP_
C2A
Ready to Stop Comp C
R
BI48
1329
Identifies if Compressor C is Ready to Stop if
the Compressor is Running (Yes / No)
RDY_STOP_
C2B
Ready to Stop Comp D
R
BI49
1330
Identifies if Compressor D is Ready to Stop if
the Compressor is Running (Yes / No)
RDY_STOP_
C3A
Ready to Stop Comp E
R
BI50
1331
Identifies if Compressor E is Ready to Stop if
the Compressor is Running (Yes / No)
RDY_STOP_
C3B
Ready to Stop Comp F
R
BI51
1332
Identifies if Compressor F is Ready to Stop if
the Compressor is Running (Yes / No)
RET_AIR_
BY_S
Active Bypass Active Sp
R
AI37
550
A Derived Value for the Current Setpoint of
the Return Air Bypass Damper on a FlexSys
Unit (%)
RET_AIR_
ENTH
Return Air Enthalpy
R
AI38
551
Actual Return Air Enthalpy (BTU/LB)
RET_AIR_
HUMD
Return Air Humidity
R
AI39
552
Actual Return Air Relative Humidity (%)
RET_AIR_
TEMP
Return Air Temp
R
AI40
553
Actual Return Air Temperature (F)
RST_ENT_
BAS
Reset Enthalpy BAS
R/W
AV47
A Value can be Provided by the BAS to Pro-
vide a Reset Enthalpy. FlexSys Only.
SAT_HIGH_
SP
SAT High Setpoint
R/W
AV26
1051
The Upper Limit for the Supply Air Tempera-
ture Setpoint on a VAV Unit (F)
SAT_LOW_
SP
SAT Low Setpoint
R/W
AV27
1052
The Lower Limit for the Supply Air Tempera-
ture Setpoint On a VAV Unit (F)
TABLE 42 -
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)