JWS-3 Embedded Installation
Connecting an JWS-3 to an IP Network
20
JWS-3 Installation and Operation Manual - P/N: 53550:Rev: A1 1/12/10
2.6 Connecting an JWS-3 to an IP Network
This allows the JWS-3 to communicate through your IP network (Internet or Intranet)
Step 1. Plug the PNET-1 surge suppressor into the JWS-3 Ethernet connector.
Step 2. Plug the RJ45 cable into the PNET-1.
Step 3. Plug the RJ45 cable into your IP network.
Figure 2.8 IP Cable Connection
Find Your Fire System Connection Option
Once the JWS-3 is connected to the IP network, connect it to either a fire alarm control panel or an
appropriate network control module. Refer to
Table 2.3, "JWS-3 to Fire System Connection
for details.
To Internet or Intranet
Customer Supplied Cable
Ethernet
Connector (J8)
PNET-1
NOTE:
The Ethernet wire must be connected to through the PNET-1 surge suppressor.
t
NOTE:
The Ethernet port is power limited.
NOTE:
Make only one of these connections.
Table 2.3 JWS-3 to Fire System Connection Options
When Connecting...
Refer to
...to a high speed NFN network consisting exclusively of
High Speed compatible panels
Section 2.7, “Connecting an JWS-3 to a High Speed
Network Control Module” on page 21
...to an NFN network
Section 2.8, “Connecting an JWS-3 to a Network Control
Module” on page 22
directly to a fire alarm control panel to be accessed
through the JWS-3
Section 2.9, “Connecting an JWS-3 Directly to a Fire
Alarm Control Panel” on page 23