SELECTION DATA
TC-16004-rev.2
4-1
4. Selection Data
4.1 Selection Guide
Refer to Engineering Manual for the Outdoor Unit.
4.2 Capacity Table
4.2.1 Cooling Capacity
■ Ducted Medium Static (EconoFresh): (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E
and (H,Y,C)IDM048B21E
TC: Total Capacity
SHC: Sensible Heat Capacity
NOTE:
Above values for (H,Y,C)IDM-B21E series indicates when unit’s air inlet is indoor air only.
Refer to Outdoor Unit Capacity Tables as actual performance data affected by indoor and outdoor unit
combination.
Indoor Air Temp
(
o
F WB)
Outdoor Air
Temp (
o
F DB)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
TC
(MBH)
SHC
(MBH)
70
31.0
25.6
31.7
25.9
32.3
26.0
32.6
26.0
33.7
26.4
34.6
26.7
35.4
26.9
80
30.2
25.2
30.7
25.4
31.2
25.5
31.6
25.6
32.6
25.9
33.5
26.2
34.3
26.5
95
28.2
24.2
28.8
24.5
29.4
24.7
30.0
24.9
31.0
25.3
32.0
25.6
32.7
25.8
110
20.2
19.8
19.8
19.5
19.4
19.2
19.0
19.0
19.2
19.2
19.3
19.3
19.4
19.4
114
17.0
17.0
16.8
16.8
16.7
16.7
16.5
16.5
16.6
16.6
16.7
16.7
16.8
16.8
118
13.8
13.8
13.9
13.9
13.9
13.9
13.9
13.9
14.0
14.0
14.0
14.0
14.0
14.0
70
37.2
31.2
38.0
31.6
38.8
31.7
39.1
31.7
40.4
32.3
41.5
32.6
42.5
32.8
80
36.2
30.6
36.8
31.0
37.4
31.1
37.9
31.3
39.1
31.6
40.2
32.0
41.2
32.4
95
33.8
29.6
34.6
29.9
35.3
30.2
36.0
30.5
37.2
30.9
38.4
31.3
39.2
31.5
110
24.2
24.0
23.8
23.7
23.3
23.3
22.8
22.8
23.0
23.0
23.2
23.2
23.3
23.3
114
20.4
20.4
20.2
20.2
20.0
20.0
19.7
19.7
19.9
19.9
20.0
20.0
20.1
20.1
118
16.6
16.6
16.6
16.6
16.7
16.7
16.7
16.7
16.7
16.7
16.8
16.8
16.8
16.8
70
49.6
41.8
50.6
42.2
51.7
42.4
52.1
42.4
53.9
43.1
55.3
43.6
56.6
44.0
80
48.3
41.0
49.0
41.3
49.8
41.5
50.5
41.8
52.2
42.2
53.6
42.8
54.9
43.3
95
45.1
39.5
46.1
39.9
47.0
40.3
48.0
40.7
49.6
41.4
51.2
41.8
52.2
42.1
110
32.3
32.1
31.7
31.7
31.0
31.0
30.4
30.4
30.6
30.6
30.9
30.9
31.1
31.1
114
27.2
27.2
26.9
26.9
26.6
26.6
26.3
26.3
26.5
26.5
26.6
26.6
26.8
26.8
118
22.1
22.1
22.2
22.2
22.2
22.2
22.2
22.2
22.3
22.3
22.4
22.4
22.4
22.4
048
71
73
030
036
Indoor
Unit
Model
61
63
65
67
69