2.13 Electrical Data
VOL: Rated Unit Power Supply Voltage (V)
PH: Phase
HZ: Frequency (Hz)
MCA: Maximum Circuit Ampacity (A)
MFA: Maximum Fuse Ampacity (A)
OPT: Rated Motor Output (kW)
FLA: Full Load Ampacity (A)
Model
Unit Main Power
Applicable Voltage
Power Supply
Indoor
Fan Motor
Unit
VOL
PH HZ Maximum Minimum
MCA
MFA
OPT
FLA
(H,Y,C)IDM030B21E
208/230
1
60
253
188
1.7
15
0.25
1.3
(H,Y,C)IDM036B21E
2.2
15
0.25
1.7
(H,Y,C)IDM048B21E
2.3
15
0.25
1.8
NOTE:
Power supply voltage should be satisfied with the following.
Supply Voltage:
Rated Voltage within ±10%
Starting Voltage:
Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%