2-8
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
< Heating Mode Operation Range >
23
(-5)
32
(0)
50
(10)
(*1)
(*2)
68
(20)
86
(30)
104
(40)
109
(43)
92
(33.5)
95
(35)
89 (32)
Air Inlet
We
t Bulb
Temperatur
e
(Outdoor
Temperature)
(
o
F (
o
C) WB
)
Air Inlet Dry Bulb Temperature
(Outdoor Temperature) (
o
F (
o
C) DB)
75
(24)
41
(5)
Normal Heating
Outdoor Air
Heating
Relative Humidity : 30%RH
Relative Humidity : 90%RH
NOTES:
1. Make sure to apply extra insulation on the unit and duct to prevent condensation when the outdoor temperature is low.
2. Make sure the air inlet wet bulb temperature (outdoor temperature) is below 59
o
F WB (15
o
C WB).
3. Outdoor air damper of this unit may remain opened at “Damper Minimum Opening” setting (optional function d7) or
prohibits OA intake for All Fresh mode below 41
o
F (5
o
C). (*1)
4. Unit may not operate when the outdoor temperature is high for All Fresh mode. (*2)
5. Compressor is stopped during outdoor air heating.
6. Air inlet dry bulb temperature (outdoor temperature) indicates the temperature detected by the unit's outdoor thermistor.
2.11 Working Range
This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump
air conditioner within this range.
< Cooling Mode Operation Range >
23
(-5)
32
(0)
50
(10)
(*1)
(*2)
68
(20)
86
(30)
104
(40)
109
(43)
92
(33.5)
95
(35)
89 (32)
64
(18)
Air Inlet
We
t Bulb
Temperatur
e
(Outdoor
Temperature)
(
o
F (
o
C) WB
)
Air Inlet Dry Bulb Temperature
(Outdoor Temperature) (
o
F (
o
C) DB)
41
(5)
Relative Humidity : 90%RH
Relative Humidity : 30%RH
Normal Cooling
Outdoor Air
Cooling
Normal Cooling
NOTES:
1. Make sure to apply extra insulation on the unit and duct to prevent condensation when the outdoor temperature is low.
2. Outdoor air damper of this unit may remain opened at “Damper Minimum Opening” setting (optional function d7) or
prohibits OA intake for All Fresh mode below 41
o
F (5
o
C). (*1)
3. Unit may not operate when the outdoor temperature is high for All Fresh mode. (*2)
4. Compressor is stopped during outdoor air cooling.
5. Air inlet dry bulb temperature (outdoor temperature) indicates the temperature detected by the unit's outdoor thermistor.