VYPER
™
VARIABLE SPEED DRIVE
OPERATION
S100-200 IOM (MAY 08)
Page 36
SETTING THE MOTOR SCREEN
Press:
[Setpoints
→
Motor]
Figure 44 - Motor Screen
Nameplate
These fi elds should be populated with the motor nameplate
information. This is for reference only.
Recycle Delay
Use the Quantum
™
LX control panel to enter a value between
0 and 80 minutes. This represents the amount of time the
Vyper
™
will remain in standby mode before initiating a shut-
down command.
Low Motor Amps
These values are generally set as shown below. The values
may be altered in accordance with individual job require-
ments.
Low Motor Amps
Delay
Shutdown
25 AMPS
30 SEC
Confi rmed Running
Motor Amps
25 AMPS
Starting Motor Amps Ignore Period
5 SEC
High Motor Amps
The High Motor Amps section is critical for protecting the
motor and the drive from high currents .
High Motor Amps
Load Inhibit
Force Unload
Delay
Warning
5 SEC
Shutdown
5 SEC
“Applied Motor FLA” Calculation
IF
USE
Mtr Nameplate SF=1.0
Mtr Nameplate FLA / 1.15
Mtr Nameplate SF=1.15
Mtr Nameplate FLA
There are several safety scenarios regarding the Vyper
™
and
the motor combination. To determine which strategy is appli-
cable, please follow the calculations in the following table.
Line
Parameter
Value
1
Applied Motor FLA
2
Applied Service Factor
1.15
3
Multiply (Line 1 x Line 2)
4
HP rating of Vyper Drive
5
Vyper Amp Limit
If Line 4 is 305/254 HP, value is 380 A
If Line 4 is 437/362 HP, value is 565 A
6
Multiply Line 5 x 1.05
• If value of Line 3 is less than value of Line 6, use Table A.
• If value of Line 3 is greater than value of Line 6, use Table B.
Table A
Parameter
Equation
Value
Load Inhibit
=Applied Motor FLA x 1.1
Force Unload
=Applied Motor FLA x 1.12
Warning
=Applied Motor FLA x 1.13
Shutdown
=Applied Motor FLA x 1.15
Содержание Frick vyper VYA PG -46
Страница 15: ...VYPER VARIABLE SPEED DRIVE INSTALLATION S100 200 IOM MAY 08 Page 15 Liquid Cooled Vyper P I Diagram Economized ...
Страница 24: ...VYPER VARIABLE SPEED DRIVE INSTALLATION S100 200 IOM MAY 08 Page 24 ANALOG BOARD WIRING Figure 21 ...
Страница 62: ...S100 200 IOM MAY 08 Page 62 VYPER VARIABLE SPEED DRIVE NOTES ...
Страница 63: ...S100 200 IOM MAY 08 Page 63 VYPER VARIABLE SPEED DRIVE NOTES ...