CONFIGURATION
Digital Auxiliaries - Timed - Run Time Control
ACCESSING:
Timed
Run Time Control
Digital Auxiliaries
DESCRIPTION:
This screen may be used to assign a digital
output to run based on the Compressor Run time.
RUN TIME DIGITAL OUTPUT CONTROL
Timed Output C - (Off or On status shown)
Enable
• Disable
- Output C will not be
enabled.
• Enable
- Output C will turn on after
the Output On times have been
met.
I/O Board
- Three selections are provided:
• None
- No board selected.
• Digital
Board
1
- The Output to
be controlled is located on Digital
Board 1.
• Digital Board 2
- The Output to
be controlled is located on Digital
Board 2.
Output On Every
- The number of hours
after the Compressor has been running,
before the Output will energize.
Output On Time
- The length of time that
the Output will be energized once the Run
Hour Interval has been satis
fi
ed.
I/O Channel
- Enter the channel of the
selected Digital Board to control (1 - 24).