QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 142
upper or maximum range (out of range) for its sensor.
High Comp. Oil Pressure Sensor Fault
- This shut-
down message is issued if the Oil Pressure reading
(analog board 1, channel 6) was to the upper or maxi-
mum range (out of range) for its sensor.
High Comp. Oil Pressure Shutdown
– The Oil Pres-
sure was greater than or equal to the High Oil Pres-
sure Shutdown setpoint for its time delay.
High Comp. Oil Temperature Shutdown
- The Oil
Temperature was greater than or equal to the High
Oil Temperature Shutdown setpoint for its time delay.
High Comp. Oil Temperature Warning
- The Oil
Temperature was greater than or equal to the High
Oil Temperature Warning setpoint for its time delay.
To access this setpoint: Menu > Setpoints > Package.
High Compressor Vib Shutdown - Suction
- If the
Suction End Compressor Vibration sensor registers a
reading that is higher than the value that has been set
for the Suction End High Shutdown, for the period of
time as set for the Suction End High Shutdown Delay,
a Shutdown will be generated.
High Compressor Vib Warning - Suction
- If the
Suction End Compressor Vibration sensor registers a
reading that is higher than the value that has been set
for the Suction End High Warning, for the period of
time as set for the Suction End High Warning Delay, a
Warning will be generated.
High Compressor Vib Shutdown - Discharge
- If
the Discharge End Compressor Vibration sensor reg-
isters a reading that is higher than the value that has
been set for the Discharge End High Shutdown, for
the period of time as set for the Discharge End High
Shutdown Delay, a Shutdown will be generated.
High Compressor Vib Warning - Discharge
- If the
Discharge End Compressor Vibration sensor registers
a reading that is higher than the value that has been
set for the Discharge End High Warning, for the pe-
riod of time as set for the Discharge End High Warn-
ing Delay, a warning will be generated.
High Disch Pres Shutdown
- The Discharge Pres-
sure was greater than or equal to the active High Dis-
charge Pressure Shutdown setpoint for its time delay.
High Disch Pres Warning
- The Discharge Pressure
was greater than or equal to the active High Dis-
charge Pressure Warning setpoint for its time delay.
High Disch Pres Shutdown -- Mode 2
–The Dis-
charge Pressure was greater than or equal to the ac-
tive High Discharge Pressure Shutdown setpoint for
its time delay.
NOTE:
This message can only be active if Dual
Discharge Pressure Mode is enabled. Also, if the
Dual Mode is enabled, then the Mode 1 safeties
are active for Modes 1 & 3, and the Mode 2 safe-
ties are active for Modes 2 & 4.
High Disch Pres Warning -- Mode 2
- The Discharge
Pressure was greater than or equal to the active High
Discharge Pressure Warning setpoint for its time de-
lay.
NOTE:
This message can only be active if Dual
Discharge Pressure Mode is enabled. Also, if the
Dual Mode is enabled, then the Mode 1 safeties
are active for Modes 1 & 3, and the Mode 2 safe-
ties are active for Modes 2 & 4.
High Discharge Pressure Sensor Fault
- This shut-
down message is issued if the Discharge Pressure
reading (analog board 1, channel 8) was to the upper
or maximum range (out of range) for its sensor.
High Discharge Temperature Sensor Fault
- This
shutdown message is issued if the Discharge Temper-
ature reading (analog board 1, channel 2) was to the
upper or maximum range (out of range) for its sensor.
High Disch Temperature Sensor Warning
– This
warning message is issued if the Discharge Tempera-
ture reading (analog board 1, channel 2) was to the
upper or maximum range (out of range) for its sensor.
High Discharge Temperature Shutdown
- The Dis-
charge Temperature was greater than or equal to the
High Discharge Temperature Shutdown setpoint for
its time delay.
High Discharge Temperature Warning
- The Dis-
charge Temperature was greater than or equal to the
High Discharge Temperature Warning setpoint for its
time delay.
High Economizer Gas Temp Sensor Warning
– This
warning message is issued if the Economizer Gas
Temperature reading was to the upper or maximum
range (out of range) for its sensor.
High Economizer Pressure Sensor Warning
– This
warning message is issued if the Economizer Pres-
sure reading (analog board 2, channel 14) was to the
upper or maximum range (out of range) for its sensor.
High Filter Pressure Sensor Warning
– This warning
message is issued if the Filter Pressure reading (ana-
log board 1, channel 7) was to the upper or maximum
range (out of range) for its sensor.
High Kw Monitoring Sensor Warning
– This warn-
ing message is issued if the Kilowatt Monitoring read-
ing (analog board 2, channel 16) was to the upper or
maximum range (out of range) for its sensor.
High Limit Disch Pres Shutdown
- The Discharge
Pressure was greater than or equal to the active High
Discharge Pressure Shutdown setpoint for its time