QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 17
motor is currently using: % (FLA x SF)
Motor Run Hours
– The total amount of
time in hours that the compressor motor
has run.
Motor Kilowatts Est.
- The actual calcula-
tion of the kilowatt usage of the compressor
motor. It is based on the calculation of KW =
(
√
3 x V x A x PF) / 1000.
SYSTEM OPERATING VALUES -
This box area al-
lows the user to customize up to six pre-de
fi
ned
data channels to display and monitor. Use this box
to show additional channels that you wish to monitor
that aren’t already provided in the other areas of this
screen. To assign these channels, press the
[Select
Data]
icon.
A menu will appear showing the pre-de
fi
ned
possible data channels. Simply click on the chan-
nel that you wish to add (NOTE: A maximum of
six may be selected at the same time):
Auxiliary Analog 1-20
Balance Piston Pressure
Capacity Slide Position
Compressor Oil Pressure
Compressor Oil Temperature
Compressor Vibration – Discharge
Compressor Vibration – Suction
Discharge Pressure
Discharge Temperature
Economizer Pressure
Filter Pressure
Intermediate Pressure
Kilowatts
Main Oil Injection Pressure
Manifold Pressure
Motor Current
Motor Stator #1 - #3
Motor Temperature – Opposite Shaft Side
Motor Temperature – Shaft Side
Motor Vibration – Opposite Shaft Side
Motor Vibration – Shaft Side
Oil Separator Temperature
Process/Brine Temperature Entering
Process/Brine Temperature Leaving
RPM
Remote Capacity Position
Remote Control Setpoint
Suction Pressure
Suction Temperature
System Discharge Pressure
Volume Slide Position
Vyper Coolant Temperature (if installed)
CAPACITY MANAGEMENT
Capacity Control
- A drop down selection box
is provided to select and display one of the fol-
lowing:
• Mode
1
• Mode
2
• Mode
3
• Mode
4
Setpoint
- A setpoint box is provided to allow
the user to set the value at which to control to.
This value is also shown in the Header on all
screens.
Actual
- This will show the Actual value of the
Control input. This value is also shown in the
Header on all screens.
COMPRESSOR (Current Start Status is shown)
Start Status
- One of the following messages
may be shown:
Ready
- The Compressor is ready to start.
Start Inhibit In Shutdown
- Compressor is
not able to start. A Shutdown alarm is pres-
ent. A Start command is required when the
unit is in Ready status.
Start Inhibit In Recycle Delay
- Compres-
sor is not able to start. The Compressor
Recycle Delay time is timing out. A Start
command is required when in the unit is in
Ready status.
Start Inhibit High Discharge Temperature
- Compressor is not able to start. The Dis-
charge temperature is above it’s Shutdown
setpoint. A Start command is required when
in the unit is in Ready status.
Start Inhibit High Oil Temperature
- Com-
pressor is not able to start. The Oil tem-
perature is above it’s Shutdown setpoint. A
Start command is required when in the unit
is in Ready status.
Start Inhibit Low Separator Temperature
- Compressor is not able to start. The Sep-
arator temperature is below it’s Shutdown
setpoint. A Start command is required
when in the unit is in Ready status.
Start Inhibit Slide Valve Too High
- This
will set the Compressor
Run Status
to Start-
ing status and then transition to Running
when the Slide Valve is below the “Highest
Capacity To Permit Starting” setpoint.
Start Inhibit Still In Prelube
- A Start com-
mand has already been sent. The Compres-
sor Run status is Starting and will transition
to Running when the oil pump pre-lube is
complete.
Start Inhibit High Suction Pressure
- The
Compressor is not able to start. The Suc-
tion pressure input is at its high end of the
sensor range. A Start command is required
when in the Ready status.
Start Inhibit High Suction/Discharge Dif-