![Johnson Controls FRICK QUANTUM HD Скачать руководство пользователя страница 120](http://html.mh-extra.com/html/johnson-controls/frick-quantum-hd/frick-quantum-hd_operation_2023218120.webp)
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 120
CONFIGURATION
Superheat
ACCESSING:
Superheat 1
Superheat Control
DESCRIPTION:
The Superheat screens are used to view
and set the operational characteristics of the Superheat
option. Each of the three screens consist of the same lay-
out:
CHANNEL CONFIGURATION
[Name]
- A user de
fi
ned name can be entered
here.
[Pressure Input]
- A pop-up box is provided to
select from the following input selections:
• Suction
Pressure
• Discharge
Pressure
•
Compressor Oil Pressure
•
Main Oil Injection Pressure
• Economizer
Pressure
• Filter
Pressure
• Intermediate
Pressure
•
Balance Piston Pressure
•
System Discharge Pressure
•
Auxiliary Analog #1 - #20
• Manifold
Pressure
[Control]
- A pop-up box is provided to select
from the following:
•
Disabled
- No Superheat control.
•
Running
- Superheat Control only con-
trols when the compressor is running.
•
Always
- Superheat control always ac-
tive.
[Temperature Input]
- A pop-up box is provid-
ed to select from the following input selections:
• Suction
Temperature
• Discharge
Temperature
•
Compressor Oil Temperature
•
Oil Separator Temperature
•
Process/Brine Temperature Entering
•
Process/Brine Temperature Leaving
•
Auxiliary Analog 1 - 10
•
EZ Cool Feedback %
•
Auxiliary Analog 12 - 20
PI CONFIGURATION
[Action]
- A pop-up box is provided to select
from the following:
•
Forward
- Will increase the output at
values greater than the Control Set-
point.
•
Reverse
- Will increase the output at
values less than the Control Setpoint.
[Setpoint]
- A setpoint box is provided to the
value that you wish to control to.