QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 96
•
Motor Temperature – Shaft Side
• Motor Temperature – Opposite Shaft
Side
•
Motor Stator #1 - #3
•
Vyper Coolant Temperature
Control
•
Disabled
- The output will be disabled.
•
Running
- The output is controlled
while the compressor is running.
•
Always
- The output is controlled
always.
I/O Board
- Three selections are provided:
• None
- No board selected.
• Digital Board 1
- The Output to be
controlled is located on Digital Board 1.
• Digital Board 2
- The Output to be
controlled is located on Digital Board 2.
On/Off When
– When operating in the (>) mode,
the digital output will be de-energized when the
analog signal falls below the Off When value, and
will remain off until the input rises above the On
When value. Similarly, when operating in the (<)
mode, the digital output will be de-energized
when the input signal exceeds the Off When
value and re-energized when the analog signal
falls below On When value.
I/O Channel
- Enter the channel of the selected
Digital Board to control (1 - 24).