![Johnson Controls FRICK QUANTUM HD Скачать руководство пользователя страница 122](http://html.mh-extra.com/html/johnson-controls/frick-quantum-hd/frick-quantum-hd_operation_2023218122.webp)
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 122
CONFIGURATION
Retransmitting Outputs
ACCESSING:
A - H
Retransmitting Outputs
DESCRIPTION:
The Retransmit Output screens (A-H and
I-P) are used to view and set the analog input assign-
ments, when it is desirable to use the retransmit feature.
Both screens consists of the same layout, with the excep-
tion of the Input Channel name:
Input Channel (to Retransmit)
- Use this pull down
menu for each channel to select the analog signal
that you would like to retransmit:
•
Capacity Slide Position
•
Volume Slide Position
• Suction
Pressure
• Discharge
Pressure
•
Compressor Oil Pressure
•
Main Oil Injection Pressure
• Economizer
Pressure
• Filter
Pressure
• Intermediate
Pressure
•
Balance Piston Pressure
•
System Discharge Pressure
• Suction
Temperature
• Discharge
Temperature
•
Compressor Oil Temperature
•
Oil Separator Temperature
•
Process/Brine Temperature Leaving
•
Process/Brine Temperature Entering
•
Remote Control Setpoint
• Motor
Current
• RPM
•
Auxiliary Analog #1 - #20
• Manifold
Pressure
•
Remote Capacity Position
•
Compressor Vibration – Suction
•
Compressor Vibration – Discharge
•
Motor Vibration – Shaft Side
•
Motor Vibration – Opposite Shaft Side
•
Motor Temperature – Shaft Side
•
Motor Temperature – Opposite Shaft Side
•
Motor Stator #1 - #3
•
Vyper Coolant Temperature
Input Value
- This will show the analog value that is
being received for a particular channel.
Output Value
- This will show the analog value that
is being sent from a particular channel.
IO Board
- Use this pull down menu to select the
source of the retransmit signal:
•
None
•
Analog Board 1
•
Analog Board 2
I/O Channel
- This will show the Output channel
(with regard to the I/O Board selection) that the re-
transmit function will be assigned to.