background image

7

Sales/Spares & Replacement Help Line 01604 762881

6. 

HEATER POSITIONING

6.1  

This heater is not suitable for external installation unless it is protected from the elements by 
a suitable enclosure. The enclosure must provide the clearance for installation, servicing and 
maintenance as well as the correct level of ventilation. The selected position should allow for a 
suitable flue system to be installed.

6.2 

When installed in a timber frame, building guidance should be taken from the Gas Industry 
Publication IGE / UP-7 (Guide for Gas Installations in Timber Frame Housing).

6.3 

BS 6798 gives details of the essential features for a compartment or cupboard where a gas 
appliance is to be installed. An existing cupboard may require modifications.

6.4 

If the heater is installed in a room containing a bath or shower it is important to locate the electrical 
switch in a position where it cannot be touched by anyone using the bath or shower. The current 
IEE Wiring Regulations (BS 7671) for England and electrical provision of the Building Regulations    
for Scotland gives details.

6.5 

Room ventilation for the heater is not necessary as the heater draws its combustion air from the 
outside of the building, cupboard or compartment ventilation is not necessary providing that the 
minimum clearances are maintained. However, reference should be made to BS 5440 Pt. 2.

 IMPORTANT: 

This appliance must be completely level. It MUST NOT lean in any direction. 

Otherwise it will cause problems with the condense draining.

7. 

HEATER COMPARTMENT CLEARANCES 

(see BS 5864)

7.1  

IMPORTANT

 - If the heater is to be fitted to an existing base duct (warm air plenum), always 

ensure when installing the appliance, the rear of the heater is aligned with the rear of the base 
duct. If there is any overhang or blanking off, it will be at the front of the heater. In any event, 
blanking plates must be mechanically secured and all joints sealed.

7.2  

When the heater is fitted into a compartment, a minimum clearance from the compartment 
walls of 3 mm (

8

”) at the sides, rear and front must be left. Where clearances are less than 75 

mm, internal surface must be lined with non-combustible material and the compartment must 
be of a fixed rigid  structure. However, there is no requirement for the use of non-combustible 
material at the front of the unit. Consideration should also be given to the space required for the 
removal and replacement of the filter tray and the entry of the gas and electrical supplies. If gas 
connections are made from a side entry, a minimum clearance of 75 mm (3”) is required at that 
side.

7.3  

For service access, a minimum of 450 mm (18”) is required at the front of the heater. Space must 
also be allowed, in a compartment installation, to permit the removal of the heater. 

7.4  

In airing cupboard installations, the part used as the air heater 7.1 must comply with the relevant 
section of BS 5864 and must be completely separated by either a non-combustible partition or 
a perforated metal partition with the perforations not exceeding 13 mm (½”). The secondary flue 
must be a tight fit where it passes through the partition and must be suitably protected (see BS 
5440: Part 1).

7.5 

In under-stairs installations, the compartment must comply with the relevant section of BS 5864, 
provided that in addition all internal surfaces (including the base) are non-combustible or lined 
with non-combustible material. This requirement is applicable only to dwellings of  more than two 
storeys.

7.6  

In free-standing installations, (refer to the instructions packed with top closure kit), only one or 
two walls will be in close proximity to the air heater; these must be non-combustible.

7.7 

Where the air heater is to be installed onto a combustible surface and under-floor ducting used, 
a suitable base tray MUST be used in order to provide insulation. 

 

NOTE:

 where a base plenum is used, no base tray is required!

7.8 

Although two permanent ventilation openings are not required, consideration should be given 
to the amount of heat emitted by any ductwork present in the compartment, otherwise the 
compartment temperature could increase and will affect the safe operation of the appliance and 
its controls.

Содержание WARMCAIR C26D

Страница 1: ...nson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS WARMCAIR C26D Condensing Air Heater High Efficiency Downflow Condensing Air Heater WarmCa...

Страница 2: ...DATES TO THIS MANUAL ARE LISTED BELOW AND SHOULD BE NOTED BEFORE COMMENCING WITH ANY INSTALLATION WORK Date of Amendment Version No Page Description 01 02 2021 ZZ1446 3 15 Invalidation of guarantee by...

Страница 3: ...Technical Data 6 6 Heater Positioning 7 7 Heater Compartment Clearances 7 8 Duct System 8 Return Air Warm Air Delivered 9 Flue Instructions 9 Flue Configurations Diagram of Terminal Positions Types o...

Страница 4: ...RAL DESCRIPTION 2 1 The WarmCair C26D is a highly efficient condensing gas fired downflow forced convection air heater Significant reductions in Low Carbon and NOx emissions are achieved It has been d...

Страница 5: ...Engineers IEE Wiring Regulations British System Design Manual Gas Fired Warm Air Heating EN Regulations No 1196 Supplementary Instructions Condensing Air Heaters 3 2 BUILDING STANDARDS AND REGULATIONS...

Страница 6: ...appliance is certified as a CAT I 2H 20 appliance 4 2 2 Gas Supply a The gas installation must be completed in accordance with the relevant standards BS 6891 b The supply must be capable of providing...

Страница 7: ...om the compartment walls of 3 mm 1 8 at the sides rear and front must be left Where clearances are less than 75 mm internal surface must be lined with non combustible material and the compartment must...

Страница 8: ...red All such rooms should be fitted with relief grilles which have a free area of 0 0088 m2 kW 1in2 250 Btu h of heat supplied to the room The only exceptions are kitchens bathrooms and WC s 8 1 4 The...

Страница 9: ...ELEVANT STANDARDS SHOULD BE FOLLOWED BS 5440 1 Flues and ventilation for gas appliances of rated heating input not exceeding 70 kW net Flues BS 5440 2 Flues and ventilation for gas appliances of rated...

Страница 10: ...5 mm E Below eaves 200 mm F Below balconies 200 mm G From a vertical drain pipe or soil pipe 150 mm H From an internal or external corner Greater than 450 mm protrusion 300 mm I Above ground roof or b...

Страница 11: ...8 1 A flue duct outlet of an appliance should be at least 600 mm from the boundary line when facing it and at least 300 mm from the boundary line when running parallel to it See Figure 6 NOTE When th...

Страница 12: ...ontal Vertical 1000 0025570 7 Flat Roof Weather Collar 1 Vertical 1000 0014900 8 Pitched Roof Collar Black 1 Vertical 1000 0014890 9 Ridge Terminal Terracotta 1 Horizontal Vertical 1000 0021030 10 Wal...

Страница 13: ...OF OPTION A Pitched Roof Collar can be fitted on a pitched roof with an angle of between 20 to 50 pitch 9 14 RIDGE TERMINAL OPTION The Ridge Terminal replaces a single 450 mm ridge tile and connects t...

Страница 14: ...connected directly to the soil stack or waste pipe there must always be either a waste trap after the tubing connections or a 75mm U trap formed within the tubing 10 1 6 Where the tubing from the pump...

Страница 15: ...BS 1362 Connections must also be in accordance with the current edition of IEE Regulations BS 7671 NOTE If for any reason the heater is re wired then 3 core cable that meets the above specification M...

Страница 16: ...ound 14 1 2 Carry out preliminary electrical system checks 14 1 3 Ensure that a the filter fan and fan compartments are free from obstructions b all registers or grilles are open and conform to design...

Страница 17: ...eriod the main burner has ignited the ESYS will show ON and the blue LED ON light on the indicator panel will remain steady 14 3 9 If the main burner fails to ignite you have 4 more attempts at igniti...

Страница 18: ...fault is indicated they should note the fault code turn off the appliance and contact a competent person which in normal circumstances would be a GAS SAFE registered engineer 15 7 Explain and demonst...

Страница 19: ...al test See Figure 17 16 2 4 For correct air heater operation the CO to CO ratio should be checked at the maximum and minimum in test mode 16 2 5 Check that the gas input is at least 90 of the nominal...

Страница 20: ...Inspect and clean the spark ignition and flame sensing electrode removing any debris and oxidization Check the spark gap and position of the spark electrode and the positioning of the flame sensing e...

Страница 21: ...W FLUE SEAL FLUE SENSOR SENSOR 45 FLYING LEADS SCREWS 16 6 HEAT EXCHANGER COMBUSTION CHAMBER 16 6 1 Refer to section 16 3 and 16 4 See Figure 29 16 6 2 Once the burner assembly has been removed inspec...

Страница 22: ...he pipe to the flue outlet 16 9 7 Refit in reverse order 16 10 CONDENSATE PUMP 16 10 1 Refer to section 16 3 See Figure 25 16 10 2 Disconnect the electrical connections on the electrical panel for Con...

Страница 23: ...n assembly and refit in reverser order 17 4 FAN FAILURE TEMPERATURE SENSOR 17 4 1 Refer to section 16 3 17 4 2 Remove the Air Circulation Fan Refer to 16 7 17 4 3 Unplug the 2 wires from the temperatu...

Страница 24: ...tlet to fill the condensate drain pipe and check for leaks Reconnect the pipe to the flue outlet IMPORTANT The condensing tube from the combustion tray MUST be routed so the tube forms a S shape makin...

Страница 25: ...a notch and the viewing window is in correct position 17 12 8 Re fit in reverse order 17 13 IGNITION ELECTRODES 17 13 1 Refer to section 16 3 See Figure 29 17 13 2 Unplug the lead from the ESYS red i...

Страница 26: ...n speed value is will display this value can be changed by pressing the A and B buttons accordingly Once the required value is reached the values can be saved as minimum by pressing button D maximum b...

Страница 27: ...sensor and wiring to control board Check operation of gas valve 2 False flame lockout False flame detected Check wiring on ESYS 3 Condense pump failure Power to the pump Check for any blockages restr...

Страница 28: ...Temperature sensor shorted to Check wiring connections not shorting to earth Check sensor resistance 44 Return air temperature sensor open circuit Temperature sensor not connected or failed Check wir...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 20 FAULT FINDING FLOW CHART...

Страница 30: ...HE CIRCULATION AIR FAN 21 1 CIRCULATION AIR FAN 21 1 1 Ensure Air Circulation Fan is running at maximum 21 1 2 A voltage should be measured and blue and yellow Voltage approx 10 VDC 21 1 3 If voltage...

Страница 31: ...X1 3 green X2 3 DSP MMI X4 3 DSP MMI green X2 1 PCB INTERFACE X2 1 black X2 4 DSP MMI X4 4 green X2 2 PCB INTERFACE X2 2 blue X2 5 DSP MMI X4 5 orange X2 3 PCB INTERFACE X2 4 yellow X3 2 PCB INTERFACE...

Страница 32: ...een F2 ESYS X3 14 purple D2 ESYS 15 BULKHEAD DUCT AIR SENSOR orange C1 ESYS X3 8 orange C2 ESYS X3 16 X1 1 2 4 5 X5 X4 X2 X3 3 6 1 2 3 4 5 1 2 3 4 1 3 DSP MMI 1 3 ESYS 10 5 1 16 8 3 6 1 15 9 9 8 7 6 4...

Страница 33: ...ares Replacement Help Line 01604 762881 23 DIMENSIONS FIGURE 34 C26D DIMENSIONS 186 106 58 46 597 21 23 342 122 1340 665 129 151 1200 485 430 381 C D 6 2 mCaire War FRONT VIEW SIDE VIEW TOP VIEW FRONT...

Страница 34: ...J24 833 7 FLUE GAS SENSOR 1 1000 0522645 J24 836 8 GAS VALVE VENTURI Includes 9 10 1 1000 0710765 J24 773 9 VENTURI GASKET 1 1000 1508285 J24 771 10 CORK GASKET 2 1000 2501175 H38 674 11 BURNER ARM AS...

Страница 35: ...833 20 COMBUSTION AIR BOX AS SEMBLY Includes 21 22 1 C26D 0132005 J24 826 21 SEALING RING 1 1000 2501685 J24 825 22 CONNECTOR SEAL 1 1000 2501715 23 CONDENSATE PUMP 1 C10D 0190005 J24 893 24 HEAT EXCH...

Страница 36: ...0516835 28 ESYS CONTROL BOX 1 1000 0525645 J24 857 29 ESYS SCREW 1 1000 3004035 J24 855 30 ESYS COVER 1 1000 0522610 J24 856 31 CONDENSATE TRAP 1 1000 0024525 J24 749 32 VERTICAL FLUE ADAPTER 60 100mm...

Страница 37: ...duct Code 1 CLEANFLOW AIR FILTER CF26 2 FILTER REPLACEMENT PADS Pack of 6 A0212X0212 3 CLEANFLOW TRANSITION KIT CTK26 4 RETURN AIR KIT Includes 4 5 RAK26 5 FLEXIBLE DUCTING 1000 0001390 6 QUICK RELEAS...

Страница 38: ...to the customer any remedial or improvement work identified during the course of commissioning or servicing work Refer to the manufacturer s helpline where assistance is needed Report product faults...

Страница 39: ...m start control Heating zone control Fitted Not required WARM AIR HEATER Has the system been balanced in accordance with the heater manufacture s instructions Yes No Was an anemometer used Yes No Yes...

Страница 40: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 41: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 42: ...NOTES...

Страница 43: ...NOTES...

Страница 44: ...Rhosili Road Brackmills Northampton NN4 7LZ sales johnsonandstarley co uk customer service johnsonandstarley co uk service johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer...

Отзывы: