18. CONTROL PANEL MODES
18.1 TEST MODE
18.1.1 To put the appliance in test mode, press Summer Air Circulation (SAC) and C buttons
together for more than 3 seconds, until the display changes. (Possible 5 second time
delay.)
t
100 is displayed along with the flame symbol.
18.1.2 Whilst in test mode, the appliance overrides all temperature setting and defaults to
maximum rate. Pressing the D and E buttons allows you to scroll between maximum
and minimum rates, whilst maintaining all protection and error conditions.
18.1.3 Press RESET to take the appliance out of test mode. If no changes are made, the
appliance will stay in test mode for 30 minutes.
18.2 AIR CIRCULATION FAN TEST MODE
18.2.1 This mode can be used to adjust the maximum and minimum fan speed output value
allowed to drive the ACF fan. (minimum value of 50 to 100 being maximum)
18.2.2 Put into fan test mode by pressing ‘C’ and ‘RESET’ for 3 seconds. The ACF fan will
run with the fan speed value showing on the LCD display, the Value from the ESYS is
bypassed.
18.2.3 On the display, letter F and the fan speed value is will display, this value can be changed
by pressing the A and B buttons accordingly. Once the required value is reached the
values can be saved as:
- minimum by pressing button D
- maximum by pressing button E
18.2.4 The display will flash for 2 seconds to confirm it has been saved to the ESYS.
18.2.5 Timeout mode is set for 30 minutes, this can be terminated by pressing RESET.
18.2.6 The backlight stays on when the test mode is active.
18.3 ERROR HISTORY MODE
18.3.1 The control panel can store the last 8 error codes. To access these codes press the
RESET button for more than 1 second, this will then flash ‘H1’ on the LCD display.
13.3.2 Error 1 being the most recent, along with the error code after the dot. To scroll though
the error history press the ‘C’ button.
18.3.3 The unit will stay in error history mode for 30 seconds.
18.3.4 To take the unit out of the error history mode press RESET.
18.3.5 In order to limit the warm air temperature the heater will shut off the burner and Lt will be
displayed in the centre of the display. This will be stored as error 57.
18.3.6 Check the filter is clean and the warm air outlets are open.
CONTROL PANEL
1
Time control
2
A +
3
B -
4
LED Display
5
E +
6
D -
7
Summer Air Circulation
8
C
9
Reset
1
2
3
4
5
6
7
9
8
FIGURE 31. CONTROL PANEL