65
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
EMAX measuring period reset
The reset of the measuring period should be carried
out via an input of the UMG 505 to run synchronized
to the energy suplliers measurement. If no reset is
carried out at the input of the UMG 505 within the
programmed measuring period, the reset is done
automatically, effected by the internal clock.
The reset of the measuring period deletes the
EMAX real power and starts a new measuring
period. The last measured EMAX real power is used
for minimum and maximum storage and, if program-
med, saved in event memory.
Synchronize internal clock
Inaccuracies of the internal clock can be corrected
by synchronization via one of the internal inputs. If
the internal input, which is assigned for
synchronicity, is active, the clock in UMG 505 will
be set to the nearest full hour.
Example 1
If the UMG 505 shows a time of 15:05h, the clock
will be corrected to 15:00h..
Example 2
If the UMG 505 shows a time of 15:35h, the clock
will be corrected to 16:00h..
CONF
Input channel 0 - 15
Synchronize clock
EMAX measuring
period reset
CONF
Input channel 0 - 15
Synchronize clock
EMAX measuring
period reset