40
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Current transformer
The ratio of the current transformer is set in configu-
ration menu
CONF
. The secondary current can
either be set to ../1A or ../5A.
If you are in configuration menu
CONF
, the current
transformer ratio can be changed as follows:
A
A
SELECT
CT
CONF
Select:
Confirm the selection
of the current
transformer menu
with
key 2.
The text
SELECT
disappears.
Set:
Select the number to
be changed using
key 1. The selected
number flashes. The
text
EDIT
appears.
Change the selected
number using
key 3.
Multiply the number
with a factor 10 with
key 2.
When the ratio of the current transformer is set,
press
key 1 as often, as no digit is flashing any
longer.
EDIT
disappears.
With
key 3 you move to the next menu. The ratio of
the current transformer is saved.
Voltage transformer
The ratio of the voltage transformer is set in confi-
guration menu
CONF
. The secondary voltage can
be set in the range of 1V up to 500V.
If you are in configuration menu
CONF,
change the
ratio of the current transformer as follows:
A
A
SELECT
CT
CONF
Select
Confirm selection of
current transformer
menu with
key 2.
The text
SELECT
disappears.
Select
With
key 3 you move
to the voltage
transformer menu.
Set
Using
key 1 the
number to be
changed is selected.
The selected number
flashes. The text
EDIT
appears.
With
key 3 the se-
lected number is
changed.
Key 2 multiplies the
number with a factor
10.
When the ratio of the voltage transformer is set,
press
key 1 as often, as no digit is flashing any
longer.
EDIT
disappears.
With
key 3 you move to the next menu. The ratio of
the voltage transformer is saved.
A
A
CT
CONF
EDIT
Secondary current
Primary voltage
Secondary voltage
kV
V
VT
CONF
EDIT
kV
V
VT
CONF
Primary current