Presettings
Current transformer, primary
CT
1A .. 999,9MA
"5000"A
Current transformer, secondary
CT
1A .. 5A
" 5" A
Voltage transformer, primary
VT
100V.. 999,9MV
" 400" V
Volrage transformer, secondary
VT
100V .. 500V
" 400" V
Aron circuit (Option)
"
nEt
"
3L, 4L
"4 L"
Data logging
"
dAtA
"
on, off
"on"
Serial interfaces
RS485, RS232, LON
RS485
(Option)
"
485
"
Baud rate
9.6, 19.2, 38.4kbps
"38.4"
Protocol
oFF, 1, 2
"01"
RS232
(Option)
"
232
"
Baud rate
9600bps, 19.2kbps, 38.4kbps
"38.4"
Protocol
oFF, 1, 2
"01"
LON (Option)
"
Lon
"
Device address
ADDR
0 .. 255
" 1"
Measured value rotation
"
Pic
"
Changing time
0 .. 9999 seconds
"0000"
Display selection
All meas. value indications No meas. value indica.
Event memory
"
Prot
"
Devices with 512k RAM
0-9999 Events
1000 Events
Net frequency
"
FrE
"
Auto, 50Hz, 60Hz
"Auto"
Switching outputs 1-5
Number
"
S.
x"
1, 2
" 1"
Limit
All measured values
"L1 0.000 A"
Minimum switching time
" . M.S"
1 .. 59 seconds
"00.01 M.S"
Exceeding
Underscoring
Switching clock
„
P.
xx“
Output channel
Switching output
„
o.
x“
0 .. 5
0 = No assignment
EMAX target number
„
S.
x“
0 .. 5
0 = No assignment
Energy meter
„
t.
xx“
00 .. 54
00 = No assignment
Switch-on time
First week day
1= Monday, .. 7= Sunday
„1xxx“ = Monday
Last week day
1= Monday, .. 7= Sunday
„x7xx“ = Sunday
Hour
00 h .. 24 h.
„xx.24 d.h.“
= inactive
Minute
00 m .. 59 m.
„00.xx m.“
Switch-off time
First week day
1= Monday, .. 7= Sunday
„1xxx“ = Monday
Last week day
1= Monday, .. 7= Sunday
„x7xx“ = Sunday
Hour
00 h .. 24 h.
„xx.24 d.h.“
Minute
00 m .. 59 m.