38
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Period of storage
The more mean values are marked for storage in
the ring buffer, the shorter becomes the period of
storage. If the ring buffer is completely full, the most
obsolete values are overwritten.
With the factory's presettings
Mean values: U1, U2, U3, I1, I2, I3, P1, P2, P3
Averaging time: 15 minutes.
The mean values of about 1 year are saved in the
device. If this period is over, the most obsolete
values are overwritten.
If various averaging times are assigned to the mean
values to be stored, more room for storage can be
required, and the period of storage can get much
shorter.
To enlarge the period of storage, the number of
saved mean values can be decreased or all mean
values can be programmed with the same averaging
time.
An
estimation
of the period of storage can be called
up in menu
PRG
.
1year, 5months, 18days, 13hours, 45minutes,
0seconds
Confirm menu PRG
with
key 2.
The symbol
SELECT
disappears.
SELECT
PRG
Scroll to indication of
period of storage with
key 2 and key 3.
In the example, the
period is estimated to
1 year and 5 months.
Y.M
D.H
M.S
PRG
Press
key 1 for about 2 seconds and you return to
the first measured value window of the measured
value indication from each program part.
Averaging time
An averaging time can be assigned to each mean
value. The following averaging times can be set:
1, 5, 10, 15, 30 seconds,
1, 5, 10, 15, 30, 60 minutes.
All averaging times are programmed to 15 minutes,
when the device leaves the factory.
Set averaging times
If the averaging time, for example, for voltage L2
should be changed to 5 seconds, please proceed as
follows in menu
PRG
:
V
L2
PRG
EDIT
Scroll to averaging
time of 5 seconds
with
key 3.
00:05 = 5 seconds
(15:00 = 15 minutes)
V
L2
PRG
EDIT
Press
key 1 for about 2 seconds and you return to
the first measured value window of the measured
value indication from each program part.
The averaging time is saved.
A
A
A
L3
L1
L2
PRG
SELECT
PRG
Confirm selection
with
key 2.
The symbol
SELECT
disappears.
The averaging times
are set to 15 minutes.
Scroll to mean values
of voltage with
key 2
and
key 3.
Select voltage in
phase L2 with
key 1.
The symbol
EDIT
appears.
Attention !
A change of the averaging time deletes the
ring buffer.