108
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Technical Data
Ambient conditions
Pollution degree
: 2
Operating temperature
: -10°C .. +55°C
Storage temperature
: -20°C .. +60°C
Humidity
: 15% .. 95% without dew
Operating height
: 0 .. 2000m over NN
Protection class
Front
: IP50 according to EN60529
Front with seal (Option)
: IP65 according to EN60529
Back side
: IP20 according to EN60529
Screw terminals
: IP20 according to EN60529
Testing voltage
Voltage measuring inputs against housing, LON, RS232 and RS485
: 3250V AC
Relay outputs, digital inputs and current measuring inputs against housing, LON, RS232 and RS485
: 2200V AC
Supply voltage Uh
: see type plate
Overvoltage class
: 300V CATIII
Range 1 (Standard)
: 85 .. 265V AC, 80 .. 370V DC
Range 2 (Option)
: 40 .. 115V AC, 55 .. 165V DC
Range 3 (Option)
: 15 .. 55V AC, 20 .. 80V DC
Fuse
: 4A up to 10 A,
Power consumption
: max. 7VA
Fuse
: 4 .. 10A
Measuring inputs
Rated pulse voltage
: 6kV
Signal frequency
: 45Hz .. 1200Hz
Current measurement
Overvoltage class
: 150V CATIII
Power consumption
: ca. 0,2 VA
Rated current at ../5A (../1A)
: 5A (1A)
Minimum working current
: 5mA
Limiting current
: 5,2A(sinus shape)
Overload
: 180A for 2 sec.
Voltage measurement
Overvoltage class
: 600V CATIII
Impedance
: 2MOhm/Phase
Power consumption
: ca. 0,1 VA
Maximum fuse: M2A
Measuring range L-N
: 50 .. 500V AC,
2,3..23VAC (Opt.)
Measuring range L-L
: 80 .. 870V AC,
4..40V AC (Opt.)
Frequency of fundamental : 45Hz..65Hz
Accuracy class according to EN61036:1996, VDE0418part 7:May 1997, IEC1036:1996
With current transformer ../5A
: Class 1
With current transformer ../1A
: Class 2
Accuracy of internal clock
: +- 1 Minute/Month