26
UMG 96RM-EL
Connection diagram, current measurement
L1
L2
L3
I1
I2
I3
L1
L2
L3
L1
L2
L3
• 3p 1w (addr. 510 = 8)
Fig. Three systems with uniform phase load-
ing. The current measurement values of the
phases of the respective system where are no
CTs connected are calculated (I2/I3 resp. I1/I3
resp. I1/I2).
Ammeter
If you want to measure the current not only with the UMG
96RM-EL but also with the ammeter, the ammeter must
be connected in series with the UMG 96RM-EL.
Fig. Current measurement with an additional
ammeter (example).
UMG
S
2
I
S
1
Einspeisung
Supply
Verbraucher
Consumer
A
(k)S
1
S
2
(l)
P
2
(L)
(K)P
1
c
Caution!
The UMG96RM is only approved for
a current measurement using the
current transformer.