40
UMG 96RM-EL
Manual setting of the subnet mask (SUb)
• When in the programming mode, press button 2 to get
to the subnet mask settings (SUb display).
• Use button 1 to select the desired digit and set
it by pressing button 2. Repeat this step for each digit
in bytes 0 to 3 in a way similar to setting the TCP / IP
device address.
• After repeated display of byte 0 (
no
digit is flashing)
one can set the gateway address.
Manual setting of the gateway address (GAt)
• When in the programming mode, press button 2 to get
to the gateway address settings (GAt display).
• Press buttons 1 and 2 to set the desired gateway ad-
dress in bytes 0 to 3 as described above.
The dynamic IP allocation must also be deactivated to
ensure that the manual settings of the TCP / IP device
address, subnet mask and gateway address are not
overwritten by a DHCP server. To do so set the parame-
ter „dyn IP“ to a value of 0 or 3 (see „IP mode configura-
tion“ table) as described under „Dynamic IP allocation“.
Dynamic IP allocation (dyn)
The dynamic allocation of the TCP / IP settings (device/
gateway address and subnet mask) provides for a fully
automated integration of the device into an existing net-
work with a DHCP server. TCP / IP settings do not need
to be configured manually as they are automatically as-
signed by the DHCP server when the device is started.
Addresses are read out in the programming mode
the same way as in the manual settings.
• Switch to the programming mode as described.
The symbols for the programming mode PRG
and the current transformer mode CT appear
on the display.
• Press button 2 several times to display the dynamic IP
allocation (dYn IP).
• Activate the parameter with button 1 (1st digit flashes)
and then select the last digit (digit flashes) with but-
ton 1. Use button 2 to set the parameter to 2 or 5 in
accordance with the „IP mode configuration“ table).
• Confirm the parameter with button 1 and exit pro-
gramming mode or wait for ca. 60 seconds.
C
Changes will only take effect after you exit
the programming mode.
Содержание UMG 96 RM-EL
Страница 13: ...13 UMG 96RM EL...
Страница 29: ...29 UMG 96RM EL...
Страница 80: ...80 UMG 96RM EL Dimensional drawings All dimensions in mm Rear view Bottom view 97 91 5...
Страница 81: ...81 UMG 96RM EL Side view 92 0 8 92 0 8 Cutout dimensions 96 max 6 42 91 5 104...
Страница 87: ...87 UMG 96RM EL...
Страница 89: ...89 UMG 96RM EL...