12
UMG 96RM-EL
Assembly
Installation location
The UMG 96RM-EL is suitable for installation in perma-
nent, weatherproof switchboards. Conducting switch-
boards must be earthed.
Installation position
The UMG 96RM-EL must be installed vertically in order
to achieve sufficient ventilation. The clearance to the top
and bottom must be at least 50 mm and 20 mm
at the sides.
Front panel cutout
Cutout dimensions:
92
+0.8
x 92
+0.8
mm.
m
Failure to comply with the minimum
spacing can destroy the UMG 96RM-EL
at high ambient temperatures!
Fig. UMG 96RM-EL
installation location
(rear view)
Mounting
The UMG 96RM-EL is mounted on the switchboard
by the side mounting brackets. These must be removed
before using the device. Mounting is carried out
by inserting and engaging the brackets.
Fig. UMG 96RM-EL
mounting bracket
(side view)
Содержание UMG 96 RM-EL
Страница 13: ...13 UMG 96RM EL...
Страница 29: ...29 UMG 96RM EL...
Страница 80: ...80 UMG 96RM EL Dimensional drawings All dimensions in mm Rear view Bottom view 97 91 5...
Страница 81: ...81 UMG 96RM EL Side view 92 0 8 92 0 8 Cutout dimensions 96 max 6 42 91 5 104...
Страница 87: ...87 UMG 96RM EL...
Страница 89: ...89 UMG 96RM EL...