Total current measurement
If the current measurement takes place via two current
transformers, the total transformer ratio of the current
transformer must be programmed in the UMG 96RM-
EL.
Example: The current measurement takes place via two
current transformers. Both current transformers have
a transformer ratio of 1000/5 A. The total measurement
is performed with a 5+5/5 A total current transformer.
The UMG 96RM-EL must then be set as follows:
Primary current:
1000 A + 1000 A = 2000 A
Secondary current:
5 A
Fig. Current measurement via a total current transformer
(example).