www.janitza.de
29
Modules 800-CT8-A | 800-CON
CAUTION
Risk of injury or damage to the device due to high
measurement currents at the connections of the
current transformers or the current measurement
inputs of the device!
High measurement currents can cause temperatures
of up to 80 °C (176 °F) on the connections of the
current transformers
·
Use wiring that is designed for an operating
temperature of at least 80 °C (176 °F)!
·
The current transformers can be hot even after
the power supply has been switched off. Allow the
connections of the current transformers and the
connecting cables to cool down before touching
them!
·
Make sure that screw terminals for the current
transformer connection on the device are
adequately tightened!
·
Ground connections present on the secondary
windings of the current transformers must be
connected to ground!
·
Observe the general safety information for
handling current transformers in the chap.
„2.7 Safety information for handling current
transformers“ on page 12.
·
Comply with the information and provisions in the
usage information of your current transformers!
WARNING
Risk of injury due to high currents and high
electrical voltages!
Severe bodily injury or death can result from:
·Touching bare or stripped leads that are
energized.
·Inputs of devices, components and modules are
dangerous to touch.
Therefore, please note for your system:
·
Disconnect the supply of power before starting
work!
·
Secure it against being switched on!
·
Check to be sure it is de-energized!
·
Ground and short circuit! Use the ground
connection points with the ground symbol for
grounding!
·
Cover or block off adjacent live parts!
JanBus interface
S1
S2
S1
S2
S1
S2
9
10
11 12
13 14
I
5
I
6
I
7
S1
S2
15 16
I
8
S1
S2
S1
S2
S1
S2
1
2
3
4
5
6
I
1
I
2
I
3
S1
S2
7
8
I
4
S1
S2
Load
L1
L2
L3
N
S1
S2
S1
S2
S1
S2
Load
L1
L2
L3
N
S2
S1
S2
S1
S2
S1
S2
S1
JanBus interface
JanBus interface
800-CT8-A module
Current measurement
Current measurement
UMG 801
(Basic device)
5.2 Example schematic diagram “Connection variants for current measurement”
Fig. Example schematic diagram, current
measurement with module 800-CT8-A