8. Module-relevant configurations
8.1 800-CT8-A module - Current transformer
Configuration on the basic device
·Press function button 1
ESC
to open the menu.
·Use buttons 2 “
5
” and 5 “
6
” to select the menu
item
Configuration
and confirm with button 3
Enter
.
·The
Configuration
window appears.
·In the
Configuration
window, use buttons 2
“
5
” and 5 “
6
” to select the menu item
Current
transformers
and confirm with button 3
Enter
.
·The
Current transformers
window appears.
Fig. Window Configuration -> item Current transformer
Ethernet (TCP/IP)
Fieldbus
Current Transformer
Voltage Transformer
Display
Configuration
ESC
·In the
Current transformers
window, choose the
item
Device
and confirm with button 3
Enter
.
·The item
Device
appears marked in “blue."
·Use buttons 2 “
5
” and 5 “
6
” to select the item for
your series module
Module 1 (up to 10 modules)
and confirm with button 3
Enter
.
Fig. Window, Current transformer module 1 -> item
Device
Device
Transformer 1..4
Transformer 5..8
Module 1
Primary
Secondary
5 A
5 A
5 A
5 A
Current transformer
ESC
·Use button 5 "
6
" to go to the setting for the
primary side of the current transformers 1-4 of the
module (current measurement inputs I1..I4).
·The item for the primary side of the current
transformers I1..I4 appears marked in “blue."
·Press button 3
Enter.
·The item for the primary side of the current
transformers I1..I4 “blinks."
·Use buttons 4 (
) and 6 (
) to change the position
of the digit to be set and buttons 2 (
5
) and 5 (
6
) to
change the digit (-1/+1).
·Confirm your entries with button 3
Enter
or end the
action by pressing button 1
ESC
.
·Use button 6 (
) to go to the configuration of the
secondary side of the current transformers I1..I4 of
the module.
·Configure the secondary side of the current
transformers I1..I4 of the module in the same way.
·Confirm your entries with button 3
Enter
or end the
action by pressing button 1
ESC
.
·Use the function buttons to configure the
Current
transformer ratio 5-8 (I5..I8)
– Primary and
secondary side – of the module, as described
above.
·To return to the menu, confirm your entries with
button 3
Enter
or end the action by pressing button
1
ESC
.
Fig. Window, Current transformer module 1 ->
item Primary for current transformer 1..4.
5 A
5 A
5 A
5 A
ESC
Device
Transformer 1..4
Transformer 5..8
Module 1
Primary
Secondary
Current transformer
INFORMATION
Before configuring the current transformer ratios,
be certain to connect the transformers in compli-
ance with the specifications on the device rating
plate and the technical data!
INFORMATION
You can also configure current and voltage
transformer ratios in the device configuration of
the
GridVis
®
page 37). A description of the
configuration can be found in the online help or in
the tutorials for the software.
Содержание 800-CT8-A
Страница 7: ...www janitza de 7 Modules 800 CT8 A 800 CON...
Страница 13: ...www janitza de 13 Modules 800 CT8 A 800 CON...
Страница 33: ...www janitza de 33 Modules 800 CT8 A 800 CON...
Страница 45: ...www janitza de 45 Modules 800 CT8 A 800 CON...
Страница 55: ...www janitza de 55 Modules 800 CT8 A 800 CON...