Xonic

®

  100  Series 

 

Jain  Technology

 

www.jain.co.kr

    Tel.  82-2-856-4114  Fax.  82-2-856-9503 

33 

7.1.6 In/Output – 
Analog Out [1] –   

Span Max 

User can use this menu to set the Span Maximum for the flow. 

 

 

 

7.1.7 In/Output – 
Analog Out [1] –

   

2mA Set 

Caution) Do NOT use this function without manufacture’s technical instructions.

 

7.2 In/Output – 

Analog Out [2] 

Same with Analog Out [1]. Please refer to above instructions.

 

Input/output 

 Relay Out [1]&[2] 

 

7.3 In/Output – 

Relay Out [1] 

In this section, user can know how to set for Relay Output. User can assign each data 
with Relay Out [1] and [2] individually. 

 

 

7.3.1 In/Output – 
Relay Out [1] –   

Output Data 

Select the data for Relay Out. 

 

 

 

 

   

7.3.2 In/Output – 
Relay Out [1] –   

Output Mode 

In the case of Open Channel, User shall use the default setting, by application.   

 

 

 
 
 

 

7.3.3 In/Output – 
Relay Out [1] –   

Duty Set 

 

 

1 . OUTPUT DATA
2 . OUTPUT MODE
3 . CALIBRATION_MIN
4 . CALIBRATION_MAX
5 . SPAN MIN
6 . SPAN MAX
7 .  2mA SET

ANALOG OUT [1]

SPAN MAX
m³/h
0

1 . OUTPUT DATA
2 . OUTPUT MODE
3 . DUTY SET
4 . REV

RELAY OUT [1]

OUTPUT DATA
1 . RELAY OFF
2 . RELAY ON
3 . HIGH FLOW
4 . LOW FLOW
5 . HIGH/LOW FLOW
6 . HIGH SPEED
7 . BATCH TOTAL

1 . OUTPUT DATA
2 . OUTPUT MODE
3 . DUTY SET
4 . REV

RELAY OUT [1]

1 . BY APPLICATION
2 . [CH 1] ONLY
3 . [CH 2] ONLY

OUTPUT MODE

1 . OUTPUT DATA
2 . OUTPUT MODE
3 . DUTY SET
4 . REV

RELAY OUT [1]

UNIT : msec

_ _ _

DUTY SET

Press [

MENU

] – 7. IN/OUTPUT –

 

1. ANALOG OUT [1] –

   

6. SPAN MAX 

 

The  value  should  be  same  with  the  maximum  flow 

user set in the menu, 5.2 Upper Flow Limit. 

 
 
 

Press [

MENU

] – 7. IN/OUTPUT –

 

1. ANALOG OUT [1] –

 7. 2mA Set

 

 

Press [

MENU

] – 7. IN/OUTPUT –

 2.ANALOG OUT [2] 

 
 
 

Press [

MENU

] – 7. IN/OUTPUT –

 3.RELAY OUT [1] 

 

Press [

MENU

] – 7. IN/OUTPUT – 3.RELAY OUT [1] – 

1. OUTPUT DATA 

 

Relay Off: Disable

 

 

Relay On: Enable

 

 

High Flow only

 

 

Low Flow only

 

 

Both of Height Flow and Low Flow   

 

Batch Total 

 
 
 
 
 

Press [

MENU

] – 7. IN/OUTPUT – 3.RELAY OUT [1] –

   

2. OUTPUT MODE 

 

By Application – Set Up by the program. 

 

[CH 1] only – Not available for Open Channel 

 

[CH 2] only – Not available for Open Channel 

 

 
 
 
 
 
 

Press [

MENU

] – 7. IN/OUTPUT – 3.RELAY OUT [1] –

   

3. DUTY SET 

 

 
 
 
 
 
 

Содержание Xonic 100 Series

Страница 1: ...Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 Technical Information Xonic 100 Series Open Channel Ultrasonic Flowmeter Open Channel Guidebook Instruction Manual...

Страница 2: ...uctions Quick Analog Output 12 Instructions Analog Input for Level Meter 14 Instructions Data Logger 16 Setting Operation General Setting 20 Setting Operation Channel Setup 22 Setting Operation Instal...

Страница 3: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 3 Delivery Items Flow Computer Transducer Bracket Cable...

Страница 4: ...r Manure Etc Steel Factory and Mining Industries Limestone Slurries Deionized Water Etc Power Plants Irrigation Canal River Stream etc Features Patented AR Mode Anti Round Specifications Principle o A...

Страница 5: ...e Name Press to change the alphabet while inputting Press to input minus sign and symbols while inputting Press to enter the choice finish inputting data Press to select the choice in menu Press to in...

Страница 6: ...concentrations of suspended solids air or a large noise component Please read this manual carefully before installation e g Open Channel Dual Path Step 1 Fixing of Mounting Bracket Selecting the right...

Страница 7: ...is measured from the CENTER of the sensor to the mounting wall In order to receive a good signal for best accuracy all transducers must face diagonally For trapezoidal or circular channels rotate the...

Страница 8: ...82 2 856 4114 Fax 82 2 856 9503 8 Step 5 Supply Power to Flow Computer Connect the power cable of the flow computer and turn on the power Step 6 Input the Values on Flow Computer Please refer to next...

Страница 9: ...Input Unit Step 2 Select the Path for introducing the Install Parameter 2 Path Select User must select the path first to setup the configuration data in other tabs Step 3 Channel Shape Setup 3 Channe...

Страница 10: ...or 2 Path Height the mounting height from the bottom 3 Path Length the length between 2 transducers Lens to Lens MAIN MENU 1 GENERAL 2 PATH SELECT 3 CH SETUP 4 INSTALL P1 5 OPERATE 6 FLOW 7 IN OUTPUT...

Страница 11: ...or a better performance 7 Reserve Install click SET for each path to enable the auto installation After setup the information for Path One User needs to go back to 2 Path Select to select other paths...

Страница 12: ...ANALOG OUT 1 or 2 ANALOG OUT 2 7 1 1 Output Data Choose the required data for output 1 None Disable 2 Flow 3 Velocity 4 Analog In 1 5 Analog In 2 7 1 2 Output Mode Depending on the measuring applicat...

Страница 13: ...nd wiring the connecting devices to the selected OUTPUT on flowmeter s PC board as below wiring diagram AO1 4 20 mA Output AO1 AO2 AO2 AI1 4 20 mA Input AI1 AI2 AI2 Flowmeter Step 3 Power On After reb...

Страница 14: ...ption User can write some description for the input data 7 5 7 Check Input Data After connected the input device user can check the input data here Step 2 Level Meter Setup In the case of Open Channel...

Страница 15: ...Step 4 Power On Check Input Data After connecting user shall see the Input data in the MAIN display as below Or user can check in the tab 7 5 7 Check Input Data to check the input data as well SITE___...

Страница 16: ...INTERNAL MEMORY 5 LOG ENABLE 2 ENABLE Step 3 Download DNW exe Download the software in user s Laptop Caution Please contact the manufacture for the software DNW allows user to 1 Output the logger dat...

Страница 17: ...Open the Device Manager on user s Laptop Find PORTS COM LPT and click Communications Port Open the tab Port Settings and click Advanced Feel free to set the COM Port Number to COM 1 COM 2 COM 3 COM 4...

Страница 18: ...t this step Run the Software DNW exe and click Configuration User will see the window of UART USB Options as below Set the Baud Rate at 115200 and the COM Port that user just set After return to DNW o...

Страница 19: ...MENU 8 DATA LOG 3 MEMORY 1 INTERNAL MEMORY 1 LOG OUTPUT 2 LOG OUTPUT Press ENT to output the data Make sure 2 ENABLE is selected on 5 LOG ENABLE menu 1 TIME SET 2 RS 232C 3 MEMORY 4 WAVE DATA DATALOG...

Страница 20: ...5 CHANNEL SHAPE 6 LEVEL METER SET SYSTEM LOCK 1 UNLOCK LOCK 2 CHANGEPASSWORD GENERAL 1 SYSTEM LOCK 2 SITENAME 3 APPLICATION 4 UNIT 5 CHANNEL SHAPE 6 LEVEL METER SET SITENAME SITE_ _ _ _ GENERAL 1 SYS...

Страница 21: ...smitter User can use either Analog In 1 or Analog In 2 for input level data If Channel is always full select Set Full Set up the input unit of the level transmitter 1 INPUT 2 UNIT LEVEL METER SET INPU...

Страница 22: ...TALL 5 OPERATE 6 FLOW 7 IN OUTPUT 8 DATALOG 9 DIAG PATH SELECT 1 PATH 1 2 PATH 2 3 PATH 3 4 PATH 4 MAIN MENU 1 GENERAL 2 PATH SELECT 3 CH SETUP 4 INSTALL 5 OPERATE 6 FLOW 7 IN OUTPUT 8 DATALOG 9 DIAG...

Страница 23: ...OPT 6 AUTO INSTALL 7 RESERVE INSTALL 8 INSTALL INFO 9 ACTUAL ZERO 0 SAMPLING CLK INSTALL 1 SENSOR TYPE 2 PATH HEIGHT 3 PATH LENGTH 4 PATH ANGLE 5 PATH HEIGHT OPT 6 AUTO INSTALL 7 RESERVE INSTALL 8 INS...

Страница 24: ...n INSTALL 1 SENSOR TYPE 2 PATH HEIGHT 3 PATH LENGTH 4 PATH ANGLE 5 PATH HEIGHT OPT 6 AUTO INSTALL 7 RESERVE INSTALL 8 INSTALL INFO 9 ACTUAL ZERO 0 SAMPLING CLK 60 000 PATH ANGLE UNIT Degree INSTALL 1...

Страница 25: ...150mm And once the level reaches the Expected Height of Path 2 300mm It will perform the installation automatically again for Path 2 How to make sure the installation is completed There are some point...

Страница 26: ...SERVE INSTALL 8 INSTALL INFO 9 ACTUAL ZERO 0 SAMPLING CLK INSTALL INFO Sensor LTR L F 0 3MHz Height 100mm Inst Path Length Not Installed INSTALL 1 SENSOR TYPE 2 PATH HEIGHT 3 PATH LENGTH 4 PATH ANGLE...

Страница 27: ...of the channel bottom to aviod false echoes from obstructions MAIN MENU 1 GENERAL 2 PATH SELECT 3 CH SETUP 4 INSTALL 1 5 OPERATE 6 FLOW 7 IN OUTPUT 8 DATALOG 9 DIAG 1 OPERATE 1 UPPER FLOW LIMIT 2 LOWE...

Страница 28: ...2 LOWER FLOW LIMIT 3 DEAD LEVEL 4 DEAD ZONE 5 FLOW AVERAGE TIME 6 TOTAL FLOW SET 7 ALARM 8 CALIBRATION 9 ENABLE AGC 0 DAMPING sec 5 FLOW AVERAGE TIME OPERATE 1 UPPER FLOW LIMIT 2 LOWER FLOW LIMIT 3 D...

Страница 29: ...TI POINT SET 3 Kc SET MULTI POINT SET 1 VIEW 2 ADD 3 DELETE 1 METHOD 2 MULTI POINT SET 3 Kc SET CALIBRATION 1 000 Kc SET Unit None OPERATE 1 UPPER FLOW LIMIT 2 LOWER FLOW LIMIT 3 DEAD LEVEL 4 DEAD ZON...

Страница 30: ...E UNIT 3 FLOW RESOLUTION 4 FLOW SCALE 5 TOTAL VOLUME UNIT 6 TOTAL RESOLUTION 7 TOTAL SCALE 8 BATCH TOTAL 9 TOTALIZER MODE 1 SECOND 2 MINUTE 3 HOUR 4 DAY FLOW TIME UNIT 1 FLOW VOLUME UNIT 2 FLOW TIME U...

Страница 31: ...FLOW SCALE 5 TOTAL VOLUME UNIT 6 TOTAL RESOLUTION 7 TOTAL SCALE 8 BATCH TOTAL 9 TOTALIZER MODE FLOW 1 xxxx 2 xxx x 3 xx xx 4 x xxx TOTAL RESOLUTION 1 FLOW VOLUME UNIT 2 FLOW TIME UNIT 3 FLOW RESOLUTIO...

Страница 32: ...9 DIAG IN OUTPUT 1 ANALOG OUT 1 2 ANALOG OUT 2 3 RELAY OUT 1 4 RELAY OUT 2 5 ANALOG IN 1 6 ANALOG IN 2 ANALOG OUT 1 1 OUTPUT DATA 2 OUTPUT MODE 3 CALIBRATION_MIN 4 CALIBRATION_MAX 5 SPAN MIN 6 SPAN MA...

Страница 33: ...5 SPAN MIN 6 SPAN MAX 7 2mA SET ANALOG OUT 1 SPAN MAX m h 0 1 OUTPUT DATA 2 OUTPUT MODE 3 DUTY SET 4 REV RELAY OUT 1 OUTPUT DATA 1 RELAY OFF 2 RELAY ON 3 HIGH FLOW 4 LOW FLOW 5 HIGH LOW FLOW 6 HIGH SP...

Страница 34: ...user s input device 1 OUTPUT DATA 2 OUTPUT MODE 3 DUTY SET 4 REV RELAY OUT 1 1 REV00 2 REV04 REV 1 SET ENABLE 2 CALIBRATION_MIN 3 CALIBRATION_MAX 4 MIN INPUT SPAN 5 MAX INPUT SPAN 6 DESCRIPTION 7 CHE...

Страница 35: ...tting for data logger 1 SET ENABLE 2 CALIBRATION_MIN 3 CALIBRATION_MAX 4 MIN INPUT SPAN 5 MAX INPUT SPAN 6 DESCRIPTION 7 CHECK INPUT DATA ANALOG IN 1 DESCRIPTION A_IN1 1 SET ENABLE 2 CALIBRATION_MIN 3...

Страница 36: ...BITS 5 LINE FEED 6 NETWORK ID CONFIGURE 1 8Bits 2 7Bits DATA BITS 1 BAUD RATE 2 DATA BITS 3 PARITY 4 STOP BITS 5 LINE FEED 6 NETWORK ID CONFIGURE 1 NO PARITY 2 EVEN PARITY 3 ODD PARITY PARITY 1 BAUD...

Страница 37: ...G TIME SYNC 7 LOG ENABLE 8 COMM MODE 9 SELECT COMM HFTA H Header S Site name N Channel No D Date C Time F Flow T Total I1 I2 AnalogIn1 2 U Unit A Alarm V Velocity FORMAT RS 232C 1 CONFIGURE 2 HEADER 3...

Страница 38: ...INTERVAL 6 LOG TIME SYNC 7 LOG ENABLE 8 COMM MODE 9 SELECT COMM 1 RS232 2 RS485 SELECT COMM 1 LOG OUTPUT 2 FORMAT 3 LOG INTERVAL 4 LOG TIME SYNC 5 LOG ENABLE 6 PORT SELECT 7 MEMORY CLEAR MEMORY LOG O...

Страница 39: ...oad the Signal Wave Data MEMORY 1 LOG OUTPUT 2 FORMAT 3 LOG INTERVAL 4 LOG TIME SYNC 5 LOG ENABLE 6 PORT SELECT 7 MEMORY CLEAR LOG ENABLE 1 DISABLE 2 ENABLE MEMORY 1 LOG OUTPUT 2 FORMAT 3 LOG INTERVAL...

Страница 40: ...evel is amplitude level of signal The value will be set and calculated automatically by the flowmeter MAIN MENU 1 GENERAL 2 PATH SELECT 3 CH SETUP 4 INSTALL 5 OPERATE 6 FLOW 7 IN OUTPUT 8 DATALOG 9 DI...

Страница 41: ...2 RISC 3 PULSE COUNT 4 GAIN LEVEL 5 HOLD FLOW 6 CONTROL HOLD FLOW Unit m h _ _ _ _ CONTROL 1 MAKEUPCONTROL 2 ANTI FAULT TIME 3 MANNING HEIGHT 4 MANNING VELOCITY 1 DISABLE 2 ENABLE MAKEUPCONTROL Press...

Страница 42: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 42 DRAWINGS...

Страница 43: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 43...

Страница 44: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 44...

Страница 45: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 45...

Страница 46: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 46...

Страница 47: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 47...

Отзывы: