Xonic
®
100 Series
Jain Technology
Tel. 82-2-856-4114 Fax. 82-2-856-9503
14
Instructions - Analog Input for Level
Meter
The flowmeter provides two 4-20 mA analog input for user. User can assign each data
with Analog In [1] and Analog In [2] individually.
Caution)
In the case of Open Channel, user needs to connect a level transmitter
and an extra Power Supply Device for the level transmitter.
Step 1:
Analog Input Setup
The standard range of output is in the 4–20 mA. User can Configure the parameters
for the input device in the tab,
7.IN/OUTPUT
.
Press [
MENU
] – 7. IN/OUTPUT –
5. ANALOG IN [1] or 6. ANALOG IN [2]
➢
7.5.1. Set Enable – Enable the function
➢
7.5.2. Calibration MIN – initial setup by manufactory.
➢
7.5.3. Calibration MAX – initial setup by manufactory.
➢
7.5.4. MIN Input Span – Introduce the minimum Level.
➢
7.5.5. MAX Input Span – Introduce the maximum Level.
➢
7.5.6. Description – User can write some description for the input data.
➢
7.5.7. Check Input Data – After connected the input device, user can check the
input data here.
Step 2:
Level Meter Setup
In the case of Open Channel, user need to connect a Level Transmitter to allow the
measurement. However, user will also need an extra power supply device to power up
the connected Level Transmitter.
➢
7.7.1. Input – User can use either Analog In [1] or Analog In [2] for input level
data.
➢
7.7.2. Unit – The unit of level transmitter is “mm” or “inch”.
MAIN MENU
1 .
GENERAL
2 .
PATH SELECT
3 .
CH SETUP
4 .
INSTALL
5 .
OPERATE
6 .
FLOW
7 .
IN/OUTPUT
8 .
DATALOG
9 .
DIAG
1 . ANALOG OUT [1]
2 . ANALOG OUT [2]
3 . RELAY OUT [1]
4 . RELAY OUT [2]
5 . ANALOG IN [1]
6 . ANALOG IN [2]
IN/OUTPUT
1 . SET ENABLE
2 . CALIBRATION_MIN
3 . CALIBRATION_MAX
4 . MIN INPUT SPAN
5 . MAX INPUT SPAN
6 . DESCRIPTION
7 . CHECK INPUT DATA
ANALOG IN [1]
MAIN MENU
1 .
GENERAL
2 .
PATH SELECT
3 .
CH SETUP
4 .
INSTALL
5 .
OPERATE
6 .
FLOW
7 .
IN/OUTPUT
8 .
DATALOG
9 .
DIAG
GENERAL
1 . SYSTEM LOCK
2 . SITE NAME
3 . APPLICATION
4 . UNIT
5 . CHANNEL SHAPE
6 . LEVEL METER SET
1 . INPUT
2 . UNIT
LEVEL METER SET
Содержание Xonic 100 Series
Страница 42: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 42 DRAWINGS...
Страница 43: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 43...
Страница 44: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 44...
Страница 45: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 45...
Страница 46: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 46...
Страница 47: ...Xonic 100 Series Jain Technology www jain co kr Tel 82 2 856 4114 Fax 82 2 856 9503 47...