-86-
P8.22
Jump frequency during
acceleration/deceleration
Disabled
0
0
☆
Enabled
1
It is used to set whether the jump frequencies are valid during acceleration/deceleration.
When the jump frequencies are valid during acceleration/deceleration, and the running frequency
is within the frequency jump range, the actual running frequency will jump over the set frequency jump
amplitude (rise directly from the lowest jump frequency to the highest jump frequency).
The following figure shows the diagram when the jump frequencies are valid during
acceleration/deceleration.