P9.41
Output terminal status upon
1st fault
It displays the status of all output
terminalswhen the latest fault occurs.
The sequence is as follows:
If an output terminal is ON, the setting is 1.
If the output terminal is OFF, the setting is
0. The value is the equivalent decimal
number converted from the DI statuses.
●
P9.42
1st faultinverter status
Reserved
●
P9.43
Power-on time upon 1st
fault
It displays the present power-on time when
the latest fault occurs.
●
P9.44
Running time upon 1st fault
It displays the present running time when the
latest fault occurs.
●
P9.47
Fault protection action
selection 1
One’s
place
Motor overload (11= E.oLt)
000
00
☆
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten’s
place
Input phase loss (12=E.IPho)
Coast to stop
0
Stop according to stop mode
1
Hundr
ed’s
place
Output phase loss(13=E.oPho)
Coast to stop
0
Stop according to stop mode
1
Thous
and's
place
External fault (15=E.EIOF)
Coast to stop
0
Stop according to stop mode
1
Ten
thous
and's
place
Communication fault
(16=E.CoF1)
Coast to stop
0
Stop according to stop mode
1
BIT4
BIT3
BIT2
BIT1
BIT0
FMP
REL1
REL2
DO1
DO2
Содержание DLB1-0004T4G
Страница 10: ... 10 Graph 1 5 5 5 7 5KW product outline dimensions Graph 1 611 18 5KW product outline dimensions ...
Страница 11: ... 11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions ...
Страница 12: ... 12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions ...
Страница 14: ... 14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram ...
Страница 15: ... 15 Graph 2 922 400KW inverter wiring diagram ...
Страница 159: ... 159 ...