Figure 18: Example Input Action
5.5.2.6.2 Programming the “Outputs” triggered by an action
Up to 8 output groups can be activated by a single action. This includes the sounder (SND-001) and Fire
Routing (FR-002) output groups.
For each activation, enter the following parameters
Activation group: Select the group to activate when the input rule is fulfilled. Choose between group 001 to
400.
Delay: Select the seconds of delay between the moment in which the input condition was fulfilled and the
activation of the input. Note that these delays are fix and are not activated/deactivated by the delays on/off
button. Select from 000 to 600 seconds of delay. Selecting 000 means immediate activation.
Hold: Populate this field if you want outputs to be active for just a brief period of time (up to 63 seconds).
Select for how many seconds do you want the output to activate. Leaving the default value 000 means that
outputs will activate for an indefinite duration (i.e. until the panel is reset).