M-P2L1-1 EN
Page 18
Release Date: November 15, 2019
Rev 01
Table 4: LED Indicators
Icon next to
the LED
LED name
Color
Status
Indication
Fire alarm
Red
Steady
ON
The panel is in “Fire alarm” state
Sounders ON
Red
Steady
ON
The sounder outputs are ON
Blinking
The sounder outputs are in delayed
activation and will activate automatically
after the delay time has expired.
Fire brigade ON
Red
Steady
ON
The FB outputs are ON
Blinking
The sounder outputs are in delayed
activation and will activate automatically
after the delay time has expired.
Delays OFF
Yellow
Steady
ON
The delays to outputs are active. I fan
alarm is processed, SND and FB outputs
will have a delayed activation.
Blinking
The system is under delayed activation
state. SND and/or FB outputs will activate
automatically after the delay time has
expired.
Fault
Yellow
Steady
ON
The system is in fault functional condition.
System fault
Yellow
Steady
ON
The CIE has detected a major malfunction
in one of its subsystems.
Disable
condition
Yellow
Steady
ON
There are disabled elements in the
system.
Test condition
Yellow
Steady
ON
The CIE is under test functional condition.
There is at least one element under test.
Sounder
fault/disable/test Yellow
Steady
ON
One or more sounder have been disabled
or are under test
Blinking
There is a fault affecting sounders.
FB output
fault/disable/test Yellow
Steady
ON
One or more FB outputs have been
disabled or are under test
Blinking
There is a fault affecting FB outputs
Power ON
Green
Steady
ON
The CIE is supplied with power (from
mains or from the battery)