M-P2L1-1 EN
Page 41
Release Date: November 15, 2019
Rev 01
6 Operation in case of alarm
When the Draco fire panel receives an alarm, it will automatically:
•
Indicate it audibly with the buzzer alarm indication
•
Activate the general fire alarm indication
•
Present the alarm screen
•
Activate the fire relay and initiate the pre-programmed output activation sequence.
6.1.
Panel’s audible alarm indication
In case of alarm, the panel will make an attention-drawing beeping sound (3 beeps per second). This audible
indication can be silenced by pushing the “panel silence” button.
6.2.
Panel’s visual alarm indications
The general fire alarm indicator
The general fire alarm visual indicator will activate immediately each time the fire panel enters into the alarm
functional condition.
The alarm screen
In the event of an alarm, non-alarm indications in the main window of the screen will be replaced by the
alarm screen. The alarm screen will always indicate the first zone which entered into alarm at the top field.
If additional zones enter into alarm, these will be shown the window below.
The zones in alarm will appear sorted from the most recent event (top) to the oldest one(bottom). Therefore,
the top field will always show the oldest zone alarm event and the field below will show the zone which
entered into alarm most recently.
The window in the rightmost part of the screen will show the total amount of zones in alarm.
The full list of initiating devices which entered into alarm can be accessed with user access level 1 (no
password) by pushing F1-”Alarms”. While the panel is in alarm, other event types such as faults or
disablement will only be presented in the LCD if interrogated using the function keys indicated at the bottom
of the screen:
F1 - Alarms
F2 – Faults
F3 – Disablements
F4 – Test conditions
F5 – Interlocking (Input-output activation) messages
The rest of menus can be accessed normally, but the fire alarm screen will be presented again within 30
seconds of no activity in the user interface.