5.4.
Operations available to users with access Level 2 and above
This chapter describes the functionalities of the panel that an operator with user access level 2 can operate.
This level of access is normally granted to users trained in the usage of fire systems. The operator level is
restricted by a three-digits password, the default password to access this level is 111. Designated user can
perform tasks by using both the functional keys and the alphanumeric keypad.
This user level will allow the operator to access all lower level menus and information and add the Operate
and Report menus by use of the 3-digit password.
Reset
To reset the Draco panel and clear all the current system settings/events, press Reset button to go back to
original standby condition. The user interface will prompt for the operator password before performing this
action.
Activate Delays
User can press the Delays ON/OFF button to activate/deactivate the sounder and fire brigade output delays.
The user interface will prompt for the operator password before performing this action.
Note that the day/night schedule can also activate and deactivate the delays at a fixed schedule. Manual
and scheduled delay activation modes are compatible with each other.
“Operate” menu tree
Under the Operate menu, personnel with user access level 2 can perform tasks related to testing and
disablements, such as run tests on zones, output groups, keyboard and indicators, and disable zone, device
or output groups accordingly. This menu also gives access to adjusting the date and time for the panel.
Users can also review the serial numbers and firmware versions of the control panel from this menu.
The sub-menu choices from the Operate menu is as follows:
1. Test zone
2. Test output group
3. Keyboard test
4. Indicators test
5. Disable zone
6. Disable output group
7. Disable device
8. Set time
9. View serial numbers and firmware versions
5.4.3.1 Test zone
This menu allows setting zones in and out of the test functional condition.
After entering user access level 2 password, use the directional keypads to move to the desired zones and
select 1 for yes and then press the Confirm key to test the designated zone(s).
When an alarm is received from a zone under test, it will be presented for 10 seconds in the panel’s user
interface and it will disappear. Alarms from zones under test will not activate outputs. These alarms will be
logged in the event log.