Press the “
M
” key to advance to
MODE 6
and immediately start lifting the loaded bucket or forks at
engine idle at smooth speed (
Open lifting valve fully to raise the load
),
DO NOT stop
the lift cycle
until
Mode
number changes from
6
to calibrated load weight entered into the system
.
(With engine at the idle speed, activate lift control valve fully, do not stop until you get weight
readout).
MODE
Five Digits Load Weight Readout Display
6
•
The display will go blank. Wait a few seconds.
•
Within a 3-5 seconds the display will show the value of the calibrated “known load weight”, in our
case 1500. If you lower the load to the ground system will go automatically into operational mode.
•
Number
8
will be shown in the
MODE
window. System is calibrated and ready to be used!
System weigh calibration function is finished!
From this point on, the system weigh calibration/setup has been successfully done and all the calibrating
parameters are saved and will not be lost when the power to the system is turned off. The display will show
the load weight value until the forks are lowered to the ground. When the forks are lowered to the ground,
the display will automatically reset and the system will go into
MODE 8
which is a starting point for all
weighing cycles.