Regency
®
Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A)
Revised 8/98
47
IZONES[1 -18].0-.7
@$41C-$42D.0-7
GET1, GET8
Interior bypassed zones
KEYSUPR[0-15]
@$491-$4A0.0
GET1
Touchpad supervision
LISTEN
@$68.3
GET1
Listen in active
LOWBAT[1-18].0-.7
@$3F8-$409.0-7
GET1
Zones low battery
LZNC[1-18].0-.7
@$2EA-$2FB.0-7
GET1, GET8
Zones low threshold trip
MDAY
@$7
GET8
Day of month (1-31)
MONTH
@$6
GET8
Month (1-12)
OPGRP
@$1A.4
GET1
Open time window group
P1SEC
@$5.4
GET1
One-second pulse
P500MS
@$5.3
GET1
Half-second pulse
PAPOUT
@$69.0
GET1
Printer out of paper
PASS1
@$74.5
GET1
True for one pass of I/O prog. each sec.
PASS10
@$74.6
GET1
True for one pass of l/O prog. every 10 secs.
PASS60
@$74.7
GET1
True for one pass of I/O prog. each min.
PHONE
@$6C.1
GET1
4140 Phone mode
REPORT
@$27.1
GET1
Reporting
RLY[1]
@$8E.0-7
GET1/PUT1,8
4180 Outputs Unit 1, P2
RLY[2]
@$8F.0 7
GET1/PUT1,8
4180 Outputs Unit 1, P3
RLY[3]
GET1/PUT1,8
4184 Outputs Unit 2, P2
RLY[4]
@$91.0-7
GET1/PUT1,8
4184 Outputs Unit 2, P3
SCR[0-7]
@$4B8-$4BF.0-7
GET1/PUT1,8
Scratch locations (See note)
SILENC
@$28.3
GET1
Silenced trouble
SMKPWR
@$EE.7
GET1
Smoke power on
SPECL
@$28.1
GET1
Special alarm
SYSTR
@$28.5
GET1
System trouble
TEE[1-8]
@$2D-$34
GET8
Area entry/exit/arm timer
TER15
@$EE.4
GET/PUT1
Output on 4720 Term 15
TER16
@$EE.3
GET/PUT1
Output on 4720 Term 16
TER18
@$12.2
GET/PUT1
Output on 4720 Term 18
TEST
@$27.6
GET1
Bell Test mode
THR
@$2
GET8
Hour of day (0-$23)
TKEY
@$62
GET8
Key input timer
TMIN
@$3
GET8
Minute of day (0-$59)
TOPEN[0-15]
@$481-$490
GET8
Touchpad door open timer
TREE
@$75.7
GET1
EEPROM trouble
TROUBL
@$26.3
GET1
Any trouble
TSEC
@$4
GET8
Second of day (0-$59)
Table 14: Status and Port Addresses
Name
Address.Point
Operations
Functions