Appendix E: Panel Connections and Wiring
51
17
+ INT SIREN
Positive (+) side of interior siren connection. 12 VDC@100 mA maximum. Other side
to - INT SIREN terminal 18. Connect multiple piezos in parallel. A 1N4001 diode (in
series) is required at each piezo location. A 4.7K ohm EOL resistor (in parallel) is reqi-
uired at the peizo or at the last peizo in a chain (see wiring diagram). This terminal nor-
mally measures zero volts (to GND).
18
- INT SIREN
Negative (-) side of interior siren connection. 12 VDC@100 mA maximum. Other side
to + INT SIREN terminal 17. This terminal normally me12 volts (to GND)
when siren is off. This is the normal monitoring (supervision) voltage.
19
GND
Interrogator 200 AVM microphone (listen-in) common ground connection
20
AVM MIC
Interrogator 200 AVM microphone (listen-in) connection
WARNING!
The maximum number of microphones to be connected to terminals 19 and 20 is two.
Connect multiple microphones in parallel.
Table E.2 Panel Terminal Strip 2 Connections
Terminal
Name
What It’s Used For
21
+12V DC
SW
Smoke and Rate-of-Rise Heat sensor power supply. Switched 12 VDC @100 mA
maximum.
22
GND
Common ground for hardwire zones 1 and 2, Smoke, and Rate-of-Rise Heat sensors
23
ZONE 1
Hardwire zone 1
24
ZONE 2
Hardwire zone 2
25
GND
Common ground for zones 3 and 4
26
ZONE 3
Hardwire zone 3
27
ZONE 4
Hardwire zone 4
28
GND
Common ground for zones 5 and 6
28
ZONE 5
Hardwire zone 5
30
ZONE 6
Hardwire zone 6
Table E.1 Panel Terminal Strip 1 Connections (Continued)
Terminal
Name
What It’s Used for