Appendix E: Panel Connections and Wiring
50
Appendix E: Panel Connections and Wiring
This appendix contains a description of the control panel terminal connections, wire recommendations, and a
typical system wiring diagram (figure E.1, last page of document). Refer to appendix F for UL requirements.
Table E.1 Panel Terminal Strip 1 Connections
Terminal
Name
What It’s Used for
1
16.5 VAC
16.5 VAC power transformer connection (or negative [-] DC connection if operating
from an external DC source or battery).
Warning
Never connect both AC power transformer and an external DC source at the same
time. Permanant damage to transformer, DC source, and panel could result.
2
16.5 VAC
16.5 VAC power transformer connection (or positive [+] DC connection if operating
from external DC source or battery). See above warning.
3
+ DC
(SIREN)
Hardwire device DC power supply. Unregulated 12-24 VDC@ 0.75 amp maximum.
Fused (F1).
Note
For 24 VDC sirens and bells only.
4
GND
Common ground connection for hardwire and other devices
5
SIREN COM
Common (C) side of external siren dry relay N/C and N/O contacts (terminals 6 and 7)
6
SIREN N/C
Normally closed (N/C) (opens on alarm) external siren dry relay contact connection
7
SIREN N/O
Normally open (N/O) (closes on alarm) external siren dry relay contact connection
8
VOICE
SIREN
One side of speaker and Interrogator 200 AVM talk-back speaker connection
Warning
The maximum number of speakers connected to terminals 8 and 9 is two. Connect
multiple speakers in series only. Connecting more than two speakers or connecting
multiple speakers in parallel could result in permanant damage to the panel.
9
VOICE
SIREN
Other side of speaker and Interrogator 200 AVM talk-back speaker connection
10
TP VOICE
Reserved for future use.
11
TP VOICE
Reserved for future use.
12
+12V DC
OUT
Superbus, Fail-to-Communicate, Interrogator 200 AVM and exterior siren DC power
supply. Regulated 12 VDC@ 0.75 amp maximum. Fused (F2).
13
BUS A
Superbus communication connection
14
BUS B
Superbus communication connection
15
GND
Superbus, AVM, FTC, etc, common ground connection
16
FTC
One side of Failure-to-Communicate (FTC) device connection. 12 VDC@100 mA
maximum. Other side to DC OUT terminal 12. (Other side to GND terminal 4 if wired to
external contact of a wireless door/window sensor.)
(continued)