General Information
Tools Required:
1. Adjustable wrench
2. 3/8” flaring tool
3. Open-end wrench (7/16”)
4. Open-end wrench (3/4”)
5. Pipe thread sealer (Non-hardening)
6. Slip-joint pliers (7”)
7. Flat blade screwdriver
8. Pipe wrench (10”)
9. 50/50 soap & water solution
10. Flashlight
System Contents:
The ISOFLAMES gas log system consists of the following items.
If any of the items below are damaged or missing, call us directly at (800) 642-2920 and we will promptly answer your call.
1. ISOFLAMES gas log burner with remote control valve
2. 3/8” x 1/2” brass supply fitting
3. Flared aluminum manifold with 3/8” brass flare nut
4. Embers
5. Gas Logs
6. Twig gas logs
7. Lava rock
8. Optional damper stop
9. Optional 3/8” x 1/2” brass elbow
10. Hand-held remote control
11. Wall Switch (Optional)
WARNING:
1. When used without fresh air, the ISOFLAMES gas log system may give off carbon monoxide, an odorless and poisonous gas.
You must make adequate air supply accessibility or provisions for combustion and ventilation; carbon monoxide poisoning may
lead to death.
2. Check the ISOFLAMES gas log system for proper gas type; the gas type will be marked on the rating plate. A liquid propane
ISOFLAMES gas log system must have a standing pilot; a manual valve or a key valve is never to be used with liquid propane.
3. The installation and provisions for combustion and ventilation air must conform with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or the CSA B 149.1, National Gas and Propane Installation Code.
4. Solid-fuels must not be burned in a fireplace where the ISOFLAMES gas log system is installed.
5. Fireplace chimney must have a permanent vent opening to the atmosphere of not less than ten inch inside diameter. (10”)
6. Fireplace must adhere to: noncombustible hearth extending minimum twenty inches (20”), noncombustible material extending a
minimum of twelve inches (12”) above the top of the fire box opening; noncombustible materials extending minimum eight inches
(8”) on both sides of fireplace opening.
7. Minimum fireplace opening must adhere to the size chart listed on next page:
Safety Instructions Prior To Installation