22
Flush Wall Finish Detail
IBVs are designed to be installed so that the rough front face of the Isokern firebox and smoke dome sit flush to the room face of
the rough framing members that create the room wall finish.
Important:
Do not build a combustible frame wall in front of the IBV firebox / smoke dome assembly. (Figure 25)
Wall Framing for the room wall where the IBV is set must not be placed across the front face of the IBV firebox and smoke dome
assembly.
Clearance to Drywall:
Drywall can be placed directly in contact with the front of the IBV firebox and smoke dome. (Figure 24)
With the Isokern firebox/smoke dome set flush with the interior face of wall framing, drywall can be hung on the framing members
and pass across the face of the IBV smoke dome and in contact with it. If necessary, the drywall can be affixed to the face of the
Isokern smoke dome with drywall screws, maximum length one inch (1”) - do not use nails.
The drywall must be cut back a minimum of two inches (2”) from the sides of the firebox opening and eight inches (8”)
back from the top of the IBV firebox opening, leaving IBV material exposed around the face of the IBV firebox opening. These
drywall cut back areas will be filled with grout in conjunction with the installation of the required fire brick lining requirements.
Figure 24
Figure 25