SECTION VII
Remote Video Terminal
Page 7.1
BP+2.9X
11/95
7.1 General
An optional remote video terminal, supplied by LorTec or by the customer, is
plugged into the optional RS232 communication or telephone modem port. If this
port was not purchased, this section does not apply to your UPS.
The remote monitor is to be a video display terminal capable of emulating a
VT100 or equivalent.
7.2 RS232 Interlace
When COM1 or COM2 user interface is selected, the basic CRT Menu
Screen looks like this during normal UPS operation. A valid password must be
entered to access this screen.
[*] UPS Normal
[ ] Transferred to Bypass
[ ] AC Input Failure
[ ] Transfer not Available
[ ] Low Battery Voltage
[ ] Battery Not Available
[ ] UPS Overloaded
[ ] Retransfer Inhibited
UPS Maintenance
Input Van
121.1
Link Voltage
400.1
Menu
Input Vbn
121.8
Battery Amps
-7.2
Input Vcn
121.0
Max Out CF
1.86
UPS
Input Ia
62.7
Output KW
0.0
Operating
Input Ib
62.5
Output KVA
1.0
Normally
Input Ic
62.6
Output PF
0.00
08/30/95
Bypass Vab
216.2
Output Van
120.1
10:07:01.314
Bypass Vbc
215.6
Output Vbn
120.3
ups normal
Bypass Vca
224.7
Output Vcn
119.9
Input Vab
210.1
Input Freq
60.00
Output Ia
3.3
Input Vbc
209.2
Output Freq
60.00
Output Ib
3.3
Input Vca
210.4
Inlet Temp
19.9
Output Ic
3.3
[N]ext [P]revious [S]ilence [U]p [D]own [E]nter [^R]efresh [H]istory
The top segment represents the LED's on the front of the UPS monitor panel.
The four-column segment represents the messages which appear on the monitor
panel's message screen. (Numbers are typical; actual values will appear.)